| 2005-06-22 00:00:00 | **********UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE 250.30 FOR GROUNDING |
| | OF TRANSFORMER AS SHOWN. |
| | PLEASE SEE THIS MUST ALSO TIE INOT |
| | EXISTING EFFECTIVE GROUNDING ELECTRODE |
| | SYSTEM. |
| | |
| | 2)NOTE: PLEASE SEE 445.13 FIR MIN SIZING |
| | OF CONDUCTORS FROM GEN. |
| | PLEASE SEE 310.16 |
| | |
| | 3)NOTE: PLEASE CORRELATE KW RATING OF |
| | GEN. FROM PLANS TO SPEC BOOK SUBMITTED. |
| | 310,300? |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE A MAIN OR MCB IN |
| | EHVAC WILL BE REQUIRED. PLEASE SEE |
| | 225.31-225.36 |
| | PLEASE INDICATE HOW AND WHICH METHOD OF |
| | DISCONNECT WILL BE TAKEN. |
| | |
| | 5)NOTE: PLEASE SEE SPECS FOR TRANSFER |
| | SWITCH SUBMITTED DOES NOT INDICATE IF |
| | EQUIPMENT IS "SERVICE ENT RATED". |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE 450.3 FOR AS MAX OCP |
| | FOR TRANSFORMER TO BE 125%. |
| | |
| | 7)NOTE: PLEASE VERIFY NEW GEN SHOWN |
| | INDICATES BEING A SEPARATELY DERIVED |
| | SYSTEM, HOWEVER AN EQUIPMENT GROUNDING |
| | CONDUCTOR IS BEING SHOWN FROM GEN TO |
| | EXIST SYSTEM? |
| | PLEASE ALSO SEE ONLY GRND ROD IS SHOWN? |
| | PLEASE SEE ANY NEW FOOTER STEEL WILL |
| | ALSO BE REQUIRED TO BE BONDED AND OR |
| | USED AS THE GROUNDING ELECTRODE IF IT |
| | MEETS 250.50. |
| | PLEASE ALSO SEE SPEC BOOK INDICATES A |
| | 3POLE ATS? |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |