| Date |
Text |
| 2005-06-15 00:00:00 | ************ UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE PLANS REFERENCE A |
| | 2003 NEC/ NFPA-70. |
| | PLEASE SEE WE ARE UNDER THE 2002 NEC AND |
| | A 2003 EDITION DOES NOT EXSIT. |
| | (MISPRINT). |
| | |
| | 2)NOTE: PLEASE SEE FAC 61G1-16.004, FAC |
| | 61G15-23.002, ALL PLANS WHICH ARE |
| | SIGNED, DATED AND SEALED BY AN ARCH OR |
| | ENGINEER IS REQUIRED TO HAVE TITLE |
| | BLOCKS WITH AS INFORMATION AS REQUIRED |
| | IN ARTICLES QUOTED ABOVE. |
| | PLEASE ALSO SEE FS 471.023 FOR CERT OF |
| | AUTH # REQUIRED. |
| | |
| | 3)NOTE: PLEASE PROVIDE LAYOUT OF AREAS |
| | CONTAINED IN NEC 516 AND LIST AREAS. |
| | |
| | 4)NOTE: PLEASE SEE ELECTRICAL PLANS |
| | SUBMITTED. PLEASE SEE PANEL SCHEDULE |
| | MENTIONS CONTINOUS @94%?? |
| | PLEASE SEE ANY CONTINUOUS LOADS ARE TO |
| | BE SHOWN @ 125%.215.3,230.42 ETC. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | EELCTRICAL PLANS. |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |