| 2005-06-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05060026 |
| | ADD: 1226 ROEBUCK CT |
| | CONT:HMR FABRICATION |
| | TEL: (386)749-4907 |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1A) THE COMPANY THAT HAS MADE |
| | APPLICATION FOR INSTALLTION OF A SPRAY |
| | BOOTH AND STRUCTURAL CHANGES TO THE CBS |
| | BUILDING DOES NOT MATCH WITH THE LICENSE |
| | FOR A SHEET METAL CONTRACTORNOR DOES THE |
| | QUALIFIER OF THE SHEET METAL COMPANY |
| | MATCHTHE SIGNATURE OF THE PERMIT |
| | APPLICATION. |
| | |
| | 1B) A SHEET METAL CONTRACTOR WILL BE |
| | WORKING OUT OF THE SCOPE OF LICENSE WHEN |
| | WORKING ON A CBS TYPE BUILDING |
| | 489.105D). |
| | |
| | 2) MOLYET ENGINEERING LLC-471.023 F.S. |
| | CERTIFICATE OF AUTHORIZATION.THE TITLE |
| | BLOCK FOR ANY SHEET BEARING THE NAME OF |
| | AN ENGINEER PRACTICING UNDER A |
| | FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ENGINEERING |
| | SERVICES, SHALL INCLUDE THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER. ADD THE NUMBER |
| | TO EACH SHEET.THIS MAY BE ADDED BY |
| | HAND. |
| | |
| | 3) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 4) ENGINEER TO PROVIDE DATA ON HOW THE |
| | EXISTING BEAM WITH NO HOOPS AND |
| | SUPPORTED BY A BLOCK WALL WILL STILL |
| | HOLD THE ROOF LOADS WITHOUT ANY |
| | ADDITIONAL REINFORCEMENT. PROVIDE WHAT |
| | TYPE OF ROOF STRUCTURE EXIST, SPAN AND |
| | LOADINGOF THIS AREA OF BEAM? |
| | |
| | 5A) THE OTHER ISSUE IS THE VERTICAL #5 |
| | REBAR, HOW DEEP DOES THE BAR HAVE TO BE |
| | DRILLED INTO THE SLAB & BEAM? WILL EPOXY |
| | BE REQUIRED? THE THIRD QUESTION IS HOW |
| | MUCH OF A CELL IS REQUIRED? |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |