| Plan Review Notes For Permit 05060011 |
| Permit Number |
05060011 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-24 00:00:00 | DENIED | | | | | | 1) SUBMIT A COPY OF THE RECORDED | | | WARRANTY DEED FOR THE NEW OWNERS AS | | | LISTED ON THE NOC. | | | | | | 2) THE UPLIFT CAPACITY FOR ITEM 'D' IN | | | THE TRUSS ANCHOR SCHEDULE ON SHEET A3 IS | | | INCORRECT. THE 2005 USP CATALOG LISTS | | | THE UPLIFT FOR A SHA6T IS -4255# FOR A | | | 2PLY MEMBER AND -6110# FOR 3 OR MORE PLY | | | MEMBERS. SOME OF THE LOCATIONS SPECIFIED | | | FOR THIS CONNECTOR ON THE ROOF FRAMING | | | PLAN EXCEED THESE UPLIFTS. | | | | | | 3) DETAIL MARK C-1/C-2 ON 6 SPECIFIED ON | | | THE ROOF PLAN AN A3 DOES NOT HAVE A | | | CORRESPONDING DETAIL MARKED AS SUCH ON | | | SHEET 6. | | | | | | 4) THE TOTAL SQUARE FOOTAGE LISTED ON | | | SHEET A-1 IS INCORRECT. IT SHOULD BE | | | 4837 S.F. | | | | | | 5) THE CALCULATED VALUE OF THE STRUCTURE | | | HAS BEEN ADJUSTED AND ADDITIONAL FEES | | | ARE REQUIRED. | | | | | | IF YOU HAVE QUESTIONS PLEASE CALL: | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|