Plan Review Notes
Plan Review Notes For Permit 05060011
Permit Number 05060011
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-24 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE RECORDED
 WARRANTY DEED FOR THE NEW OWNERS AS
 LISTED ON THE NOC.
  
 2) THE UPLIFT CAPACITY FOR ITEM 'D' IN
 THE TRUSS ANCHOR SCHEDULE ON SHEET A3 IS
 INCORRECT. THE 2005 USP CATALOG LISTS
 THE UPLIFT FOR A SHA6T IS -4255# FOR A
 2PLY MEMBER AND -6110# FOR 3 OR MORE PLY
 MEMBERS. SOME OF THE LOCATIONS SPECIFIED
 FOR THIS CONNECTOR ON THE ROOF FRAMING
 PLAN EXCEED THESE UPLIFTS.
  
 3) DETAIL MARK C-1/C-2 ON 6 SPECIFIED ON
 THE ROOF PLAN AN A3 DOES NOT HAVE A
 CORRESPONDING DETAIL MARKED AS SUCH ON
 SHEET 6.
  
 4) THE TOTAL SQUARE FOOTAGE LISTED ON
 SHEET A-1 IS INCORRECT. IT SHOULD BE
 4837 S.F.
  
 5) THE CALCULATED VALUE OF THE STRUCTURE
 HAS BEEN ADJUSTED AND ADDITIONAL FEES
 ARE REQUIRED.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714