| Plan Review Notes For Permit 05051989 |
| Permit Number |
05051989 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-02 00:00:00 | ********* UNSAT 3RD REVIEW ********** | | | | | | 1)NOTE: PLEASE SEE SAME NOTES FROM | | | PREVIOUS TWO REVIEWS STILL HAVE NOT BEEN | | | ADDRESSED. | | | NO CHANGES HAVE BEEN MADE TO ELECTRICAL | | | PLANS. | | | | | | 2)NOTE: PLEASE SEE NEW LOAD CALCUALTIONS | | | SUBMITTED NOW INDICATE A NEW POOL SUB | | | PANEL IS GOING TO BE INSTALLED. | | | PLEASE CORRELATE ELECTRICAL PLANS AND | | | INFORMATION SUBMITTED. | | | | | | 3)NOTE: PLEASE SEE LOAD CALCULATIONS | | | SHALL CONTAIN THE PRINTED NAME AND | | | SIGNATURE OF THE EPRSON RESPONSIBLE FOR | | | PLANS. | | | | | | 4)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B). | | | IF PLANS COME BACK IN WITH OUT ANY OF | | | THE CODE COMPLIANCE COMMENTSADDRESSED, | | | A 4X FEE SHALL BE ACCESSED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|