Plan Review Notes
Plan Review Notes For Permit 05051989
Permit Number 05051989
Review Stop E
Sequence Number 3
Notes
Date Text
2005-09-02 00:00:00********* UNSAT 3RD REVIEW **********
  
 1)NOTE: PLEASE SEE SAME NOTES FROM
 PREVIOUS TWO REVIEWS STILL HAVE NOT BEEN
 ADDRESSED.
 NO CHANGES HAVE BEEN MADE TO ELECTRICAL
 PLANS.
  
 2)NOTE: PLEASE SEE NEW LOAD CALCUALTIONS
 SUBMITTED NOW INDICATE A NEW POOL SUB
 PANEL IS GOING TO BE INSTALLED.
 PLEASE CORRELATE ELECTRICAL PLANS AND
 INFORMATION SUBMITTED.
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS
 SHALL CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE EPRSON RESPONSIBLE FOR
 PLANS.
  
 4)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B).
 IF PLANS COME BACK IN WITH OUT ANY OF
 THE CODE COMPLIANCE COMMENTSADDRESSED,
 A 4X FEE SHALL BE ACCESSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  