Plan Review Notes
Plan Review Notes For Permit 05051989
Permit Number 05051989
Review Stop E
Sequence Number 2
Notes
Date Text
2005-08-16 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE NOTE # 1 FROM
 PREVIOUS REVIEW.
 NO CHNAGES WERE MADE TO PLANS??
 PLEASE SEE NO CONDUITS, CONDUCTORS,
 DISCONNECT ETC SHOWN FOR NEW HEAT PUMP.
  
 2)NOTE: PLEASE SEE FS 472.025 WHICH
 REQUIRES THE SURVEY TO CONTAIN THE
 ORIGINAL SIGNATURE AND SEAL FROM THE
 LICENSED SURVEYOR.
 FAC 61G17-7.002
 PLEASE WAS NOT PART OF ANY OF THE
 ORIGINAL COMMENTS, HOWEVER PLANS ARE
 GOING BACK AT THIS TIME, PLEASE SEE BLDG
 REVIEW COMMENTS FOR THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]