| Plan Review Notes For Permit 05051989 |
| Permit Number |
05051989 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-08 00:00:00 | *********** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE PLANS MENTIONS A NEW | | | HEAT PUMP, HOWEVER NO FEEDERS, CONDUITS | | | OCP ETC IS SHOWN. | | | 215.5 | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCAULTIONS | | | SHOWING ALL NEW ELECTRICAL EQUIPMENT | | | INCLUDING HEAT PUMP. PLEASE SEE ALL | | | CONTINUOUS LOADS ARE TO BE SHOWN @ 125%. | | | 215.3,230.42, ETC. | | | | | | 3)NOTE: PLEASE CORRELATE PERMIT | | | APPLICATION WITH PLANS FOR PERMIT | | | DISCRIPTION TO INCLUDE HEAT PUMP ETC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORAMTION FOR | | | REVIEW.IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|