| Date |
Text |
| 2005-07-11 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED NOTICE OF COMMENCEMENT. |
| | |
| | 2- UPDATE GENERAL NOTES IN SHEET T1. SEE |
| | CHAPTER 35 FOR PROPER REFERENCE AND |
| | EDITION. |
| | |
| | 3- DESIGN PARAMETERS: WHY MINIMUM SOIL |
| | BEARING PRESSURE IS NA?. |
| | |
| | 4- PROVIDE SPECIFICATIONS FOR COLUMNS AT |
| | MASTER BEDROOM BAY WINDOW. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 5- PROVIDE COMPLETE SPECS AND LISTING |
| | FOR BBQ TO BE INSTALLED IN PORCH. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001 |
| | AND SECTION 2808 FBC 2001. |
| | |
| | 6- FOOTING DETAIL #5 DOESN'T MATCH |
| | FOOTING BETWEEN GARAGE AND CLUB ROOM. |
| | |
| | 7- PLANS SUBMITTED ARE SPECIFYING LOT 3. |
| | APPLICATION IS FOR LOT 20. REVISE PLANS. |
| | |
| | 8- REVISE/UPDATE ALL TRUSS ANCHORS |
| | SPECIFYING SAME SIZE AND NUMBER OF NAILS |
| | AS SHOWN ON CATALOGUE THAT WAS REVISED |
| | TO COMPLY WITH SEC. 1609.4.3 FBC 2001. |
| | OTHERWISE, PROVIDE TESTING & ENGINEERING |
| | FOR NAIL SIZE AND NUMBER THAT DIFFER |
| | FROM THOSE ALREADY TESTED AND PUBLISHED |
| | BY THE MANUFACTURER. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 9- CONNECTOR THD210 IS A WOOD TO WOOD |
| | CONNECTOR. SEE CATALOGUE FOR PROPER |
| | MASONRY CONNECTOR. |
| | |
| | 10- DETAIL E/A3: CLARIFY WHY SPECIFYING |
| | EXP. BOLTS INTO CONCRETE. THERE IS NOT |
| | ATTACMENT TO CONCRETE. |
| | |
| | 11- CLEARLY SPECIFY MULLION SIZE AND |
| | ANCHORS FOR BIG WINDOWS AT LIVING ROOM. |
| | SEE PRODUCT APPROVAL TO VERIFY THAT |
| | ANCHOR SIZE WILL MEET THE CALCULATED |
| | DESIGN PRESSURES. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 12- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) SLIDING GLASS DOORS. FLORIDA APPROVAL |
| | SUBMITTED DOESN'T MATCH DADE COUNTY NOA |
| | SUBMITTED. |
| | |
| | B) FIXED WINDOWS. 2 DIFFERENT DADE |
| | COUNTY NOA'S WERE SUBMITTED. SELECT ONLY |
| | ONE. |
| | |
| | C) CASEMENT WINDOWS. NEED FLORIDA |
| | PRODUCT APPROVAL. |
| | |
| | D) WINDOW MULLION FOR LIVING ROOM FIXED |
| | WINDOWS. SPECIFY SIZE AND FASTENERS. |
| | |
| | 13- SOIL TEST REPORT SUBMITTED IS FOR |
| | LOT 3. NEED ONE FOR LOT 20. |
| | |
| | 14- SURVEY DOESN'T MATCH PLANS. REVISE |
| | AS REQUIRED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT(561)805-6712. |