| Plan Review Notes For Permit 05051930 |
| Permit Number |
05051930 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-07 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE RISER SHOWS #3 FEEDERS TO PANEL | | | "C", THE SCHEDULE LISTS #6 ON A 100 AMP | | | BREAKER. PLEASE CORRECT. NOTE PANEL "C" | | | HAS A 87 AMP LOAD, 4.25 ON PANEL "A" | | | SHEDULE/CALC. CORRECT CALC AND SCHEDULE. | | | | | | 2} THE RECEPTACLES ON THE KITCHEN ISLAND | | | | | | MUST BE GFI PER 210.8(A)(6). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|