| 2005-07-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- UPDATE GENERAL NOTES IN SHEET T1. SEE |
| | CHAPTER 19 AND 35 FBC 2001 FOR PROPER |
| | STANDARD REFERENCE AND EDITION. ALSO, |
| | SEE SEC. 2405.2 FBC 2001 AND REVISE |
| | SAFETY GLAZING NOTE AS REQUIRED. |
| | |
| | 3- DESIGN PARAMETERS: WHY MINIMUM SOIL |
| | BEARING PRESSURE IS : NA?. |
| | |
| | 4- PROVIDE COMPLETE BBQ SPECS AND |
| | LISTING FOR INSTALLATION IN PORCH. SEC. |
| | 2808 FBC 2001. |
| | |
| | 5- FOOTING BETWEEN GARAGE AND CLUB ROOM |
| | DON'T MATCH DETAIL 5. REVISE AS REQUIRED |
| | |
| | 6- REVISE/UPDATE ALL TRUSS ANCHORS NAIL |
| | SIZE AND NUMBER TO MATCH CATALOGUE THAT |
| | WAS REVISED TO COMPLY WITH SEC. 1609.4.3 |
| | FBC 2001. PROVIDE TESTING & ENGINEERING |
| | FOR TYPE AND NUMBER OF NAILS THAT DIFFER |
| | FROM THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 7- CONNECTOR THD210 IS A WOOD TO WOOD |
| | CONNECTOR. SEE CATALOGUE FOR PROPER |
| | MASONRY CONNECTOR AND REVISE AS REQ'D. |
| | |
| | 8- SPECIFY MULLION SIZE AND ANCHORS FOR |
| | FIXED WINDOWS AT LIVING ROOM. SIZE OF |
| | MULLION SHOWN ON PRODUCT APPROVAL |
| | SUBMITTED DOESN'T RESIST THE DESIGN |
| | PRESSURES CALCULATED ON PLANS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) SLIDING GLASS DOORS. DADE COUNTY NOA |
| | AND FLORIDA REPORT DON'T CORRESPOND TO |
| | EACH OTHER. |
| | |
| | B) WINDOW MULLION SIZE AS SPECIFIED ON |
| | PLANS FOR LIVING ROOM WINDOWS. |
| | |
| | C) CASEMENT WINDOWS. NEED THE FLORIDA |
| | PRODUCT APPROVAL PART. MAKE SURE DADE |
| | COUNTY NOA MATCHES FLORIDA REPORT AND |
| | ASSEMBLY SHOWN ON PLANS. |
| | |
| | D) ROOF TILE. NEED FLORIDA PRODUCT |
| | APPROVAL. MAKE SURE REPORT SUBMITTTED IS |
| | THE SAME ONE SUBMITTED FOR FLORIDA |
| | PRODUCT APPROVAL. |
| | |
| | 10- OWES #206.76 FOR UPDATED VALUATION. |
| | GUEST ROOM WAS NOT CONSIDERED IN A/C |
| | AREA DECLARED IN APPLICATION. |
| | |
| | 11- SPECIFY COLUMNS AT MASTER BEDROOM |
| | BAY WINDOW. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. SEE SHEET A1. |
| | |
| | 12- DETAIL E/A3: CLARIFY WHY USING 6" |
| | BOLTS INTO CONCRETE. THERE IS NOT |
| | CONCRETE TO ATTACH TO. REVISE AS REQ'D. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |
| | |