| 2005-09-13 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05051913 |
| | ADD: 1645 PALM BCH LAKES #1200 |
| | CONT:)(PLAN REVIEW) CONTRACTOR TO |
| | |
| | BE DECIDED |
| | TEL: (561)706-7201 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) COMMENT# 1 FROM THE FIRST REVIEW, |
| | PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | |
| | 2) COMMENT# 3 FROM THE PEVIOUS REVIEW, |
| | NOTE FOR ALL THREE FLOORS!!!!! |
| | 412.6.1 ALL ELEVATORS ON ALL FLOORS |
| | SHALL OPEN INTO ELEVATOR LOBBIES WHICH |
| | ARE SEPARATED FROM THE REMAINDER OF THE |
| | BUILDING BY 1-HOUR FIRE RESISTANT |
| | CONSTRUCTION WITH 20-MINUTE OPENING |
| | PROTECTIVES. |
| | EXCEPTIONS: |
| | 1. ELEVATOR LOBBIES WITHIN AN ATRIUM. |
| | 2. WHERE THERE ARE OPEN EXTERIOR |
| | CORRIDORS THE ENTIRE WIDTH OF THE |
| | BUILDING WITH STAIRS LOCATED AT EACH END |
| | AND THE ELEVATORS ARE LOCATED ON THE |
| | EXTERIOR OF THE BUILDING. |
| | 3.THE MAIN ENTRANCE LEVEL OF THE |
| | BUILDING. |
| | |
| | 412.6.2 OPENINGS IN THE ELEVATOR LOBBY |
| | SHALL BE LIMITED TO THOSE REQUIRED FOR |
| | ACCESS TO THE ELEVATORS AND FOR EGRESS |
| | FROM THE BUILDING. ALL ROOMS AND |
| | ENCLOSURES SHALL HAVE AT LEAST ONE |
| | REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL |
| | THROUGH THE ELEVATOR LOBBY.OPENINGS |
| | MAY BE PROVIDED WITH HORIZONTAL SLIDING |
| | DOORS CONFORMING TO 1012.4.EXIT |
| | STAIRWAYS, CHUTES, JANITOR CLOSETS, |
| | GUEST ROOMS, SERVICE ROOMS, ETC., SHALL |
| | NOT OPEN INTO THE ELEVATOR LOBBY. |
| | |
| | 412.6.3 EACH ELEVATOR LOBBY SHALL BE |
| | PROVIDED WITH AN APPROVED SMOKE |
| | DETECTOR LOCATED ON THE LOBBY CEILING. |
| | WHEN THE DETECTOR IS ACTIVATED, |
| | ELEVATOR DOORS SHALL NOT OPEN AND ALL |
| | CARS SERVING THAT LOBBY ARE TO RETURN TO |
| | THE MAIN FLOOR AND BE UNDER MANUAL |
| | CONTROL ONLY.IF THE MAIN FLOOR |
| | DETECTOR OR A TRANSFER FLOOR DETECTOR IS |
| | ACTIVATED, ALL CARS SERVING THE MAIN |
| | FLOOR OR TRANSFER FLOOR SHALL RETURN TO |
| | A LOCATION APPROVED BY THE FIRE |
| | DEPARTMENT AND BUILDING OFFICIAL AND BE |
| | UNDER MANUAL CONTROL ONLY.THE DETECTOR |
| | MAY SERVE TO CLOSE THE LOBBY DOORS. |
| | |
| | THESE COMMENTS ABOVE DEAL WITH COMMENTS |
| | 3,4 & 8FROM THE PREVIOUS REVIEW. |
| | 412.6.2 ACTUALLY DEALS WITH (2) ISSUES |
| | THE FIRST STATING THAT ALL ROOMS SHALL |
| | HAVE AT LEAST ONE MEANS OF EGRESS TO A |
| | EXIT WITHOUT HAVING TO TRAVEL THROUGH A |
| | ELEVATOR LOBBY. THERE ARE NO EXCEPTIONS |
| | TO FEASIBLITY TO COMPLY. THERE ARE THREE |
| | EXCEPTIONS LISTED ABOVE WHICH ARE NOT |
| | REQUIRED TO COMPLY WITH THIS SECTION. |
| | |
| | THE SECOND ISSUE WITH 412.6.3 DEALS |
| | WITH WHICH OPENINGS ARE ACCEPTIBLE TO BE |
| | IN A ELEVATOR LOBBY AND WHICH AREN'T. |
| | EXIT STAIRWAYS, CHUTES, JANITOR CLOSETS, |
| | GUEST ROOMS, SERVICE ROOMS, ETC., SHALL |
| | NOT OPEN INTO THE ELEVATOR LOBBY. |
| | |
| | |
| | 3)COMMENT# 6 FROM THE PREVIOUS REVIEW,6) |
| | DOORS THAT DO NOT MEET THE MANEUVERING |
| | CLEARENCES AT DOORS ARE: |
| | A824- AUTO CLOSER, ROOMS 812, 813 & 814. |
| | |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | THE CODE IS VERY CLEAR WHERE THERE IS |
| | EXISTING ACCESSIBILITY ISSUES, THE |
| | TENANT IN THIS CASE HAS A DUTY TO |
| | CORRECT THE EXISTING VIOLATIONS TO THE |
| | EXTENT OF 20% OF THE CONTRACT VALUE. |
| | |
| | 11-4.1.6(2)(A)(I)AN ACCESSIBLE ENTRANCE |
| | DOOR A824 CAN COUNT PART OF THE |
| | DISPROPORTIONATE COST IF YOU INDICATE ON |
| | THE E PAGES THE ELECTRICAL CIRCUIT |
| | REQUIRED TO OPERATE THE DOOR, ALSO |
| | PROVIDE SPEC ON HARDWARE. |
| | |
| | 11-4.1.6(2)(A)(II)AN ACCESSIBLE ROUTE: |
| | DOORS 8112,813 & 814 ALSO NEED TO COMPLY |
| | BY REARRANGING THE CONFIGURATION.THERE |
| | IS STILL DUTY TO COMPLY IF THE 20% OF |
| | THE CONTRACT VALUE HAS NOT BEEN MEET. |
| | PROVIDE INFORMATION AS TO WHERE THE |
| | ADDITIONAL FUNDS ARE TO BE DISPERSED. |
| | |
| | 11-4.1.6(2)(A)(III) DEALS WITH RESTROOMS |
| | THAT WOULD NEED TO BE UPGRADED.BELOW IS |
| | THE ACTUAL COST BREAK OUT TO INDICATE |
| | HOW THE 20% IS TO BE SPENT. |
| | |
| | 11-4.1.6(2) DUTY TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| | AREAS SHALL BE DEEMED DISPROPORTIONATE |
| | TO THE OVERALL ALTERATION WHEN THE COST |
| | EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| | TION TO THE PRIMARY FUNCTION AREA. |
| | (A)(I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | |
| | |
| | 4) COMMENT# 9A FROM THE PREVIOUS REVIEW, |
| | AS STATED ABOVE INDICATE THE AUTOMATIC |
| | DOOR OPENER FOR A824 ON BOTH THE A & E |
| | SHEETS, PROVIDE SPECIFICATIONS FOR SUCH |
| | HARDWARE. IF THE ELECTRIC GOES OUT, WILL |
| | THIS DOOR AUTOMATICLLY OPEN OR WILL IT |
| | BE PUT ON THE GENERATOR EMERGENCY |
| | CIRCUITS? |
| | |
| | |
| | 5) COMMENT 5, 10 & 12 FROM THE PREVIOUS |
| | REVIEW, DEALS WITH STENCILING OF RATED |
| | WALLS, BUT I COULD NOT FIND WHERE THE |
| | REVISION WAS MADE WITH EITHER A DELTA OR |
| | CLOUD? |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |