Plan Review Notes
Plan Review Notes For Permit 05051913
Permit Number 05051913
Review Stop P
Sequence Number 1
Notes
Date Text
2005-06-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS CS, AND A1.1 THRU A4.3 THE
 PRINTED NAME OF THE PERSON SEALING THE
 SHEETS SHALL BE ON THE TITLE BLOCK. FAC
 61G1-16.004(6) AND FS 481.2055
 2. ALL MEP SHEETS, CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE
 BLOCK OF THE ARCHITECTURAL BUSINESS. FAC
 61G1-16.004(2) AND FS 481.2055
 3. SHTS A1.1, A1.2, & A1.3 DEMOLITION
 KEY NOTES TO BE SPECIFIC TO EACH SHEET.
 WORK ON EACH SHEET IS DIFFERENT. SHT
 A1.2 DOES NOT APPEAR TO HAVE PLUMBING
 WORK, AND SHT A1.3 SHOWS PLUMBING WORK,
 BUT NO DEMO KEY NOTES OR DEMO KEY NOTE
 NUMBER IDENTIFYING THE WORK SHOWN.
 PLEASE CLARIFY. SECTION 104.2.1.
 4. SHT A2.1 SHOW THE CLEAR FLOOR SPACE
 FOR THE SINKS IN ROOMS 805 & 820. CLEAR
 FLOOR SPACE SHALL BE FORWARD APPROACH
 AND EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK. CABINET DOORS ARE NOT APPROVED
 IN THE CLEAR FLOOR SPACE. SECTION
 11-4.24.5.
 5. SHT A2.2 & A2.3 ROOMS 1112 AND 1224
 INDICATES NEW CABINETS. SINKS SHALL
 COMPLY WITH 11-4.24 AND ALL SUBSECTIONS.
 SHOW CLEAR FLOOR SPACE REQUIRED BY
 SECTION 11-4.24.5. CLEAR FLOOR SPACE
 SHALL BE FORWARD APPROACH AND SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. CABINET DOORS ARE NOT APPROVED IN
 THE CLEAR FLOOR SPACE.
 7. SHT A4.1 DETAILS 3, 7, & 8. SINKS
 SHALL BE ACCESSIBLE PER SECTION 11-4.24.
 SHOW THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.4.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE
 E. 11-4.24.6 EXPOSED PIPES AND SURFACES
 F. 11-4.24.7 FAUCETS
 8. SHT P1.1 WATER ISOMETRIC. WATER
 HAMMER ARRESTORS ARE REQUIRED ON THE
 WATER LINES TO THE DISH WASHER AND THE
 ICE MAKER IN THE REF. SECTION 604.9.
 LOCATION OF THE WATER HAMMER ARRESTORS
 SHALL BE NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201.
 9. SHT P1.1 GENERAL NOTES: #16 AIR
 CHAMBERS ARE NOT APPROVED. SECTION 604.9
 DELETE NOTE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]