| Plan Review Notes For Permit 05051913 |
| Permit Number |
05051913 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-29 00:00:00 | DENIED:PLAN CHECK | | | 1.PLAN SHEET M2.1, EXISTING DUCT | | | PENETRATING OFFICE #802 AND ADJOINING | | | SPACE, FIRE DAMPER REQUIRED.PLEASE | | | VERIFY EXISTING FIRE DAMPER & ANNOTATE | | | ON PLAN. | | | | | | 2.PLAN SHEET M2.2, EXISTING DUCT | | | PENETRATING ELEVATOR LOBBY & RECEPTION | | | AREA WALL.PLEASE VERIFY FIRE DAMPER. | | | PLAN DOES NOT INDICATE NEW OR EXISTING | | | DAMPER. | | | | | | PLEASE NOTE, NO COMBUSTIBLES ALLOWED | | | ABOVE THE CEILING IN THE RETURN AIR | | | PLENUM PER 2001FBC(M)602.2.1. | | | | | | SEE COMMENT #1 BY PLUMBING & ELECTRICAL | | | PLAN REVIEWERS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|