Plan Review Notes
Plan Review Notes For Permit 05051913
Permit Number 05051913
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051913
 ADD: 1645 P. B. LAKES BLVD
 SUITES: 800
 1150
 1200
 CONT: D. B. MARCUS CONST
 TEL: (561)346-5667
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) CS- PROJECT DATA INDICATES
 CONSTRUCTION TYPE TO BE TYPE V
 UNPROTECTED? HIGH RISE EITHER TYPE I OR
 II FULLY SPRINKLERED.
  
 3) NOTE FOR ALL THREE FLOORS!!!!!
 412.6.1 ALL ELEVATORS ON ALL FLOORS
 SHALL OPEN INTO ELEVATOR LOBBIES WHICH
 ARE SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY 1-HOUR FIRE RESISTANT
 CONSTRUCTION WITH 20-MINUTE OPENING
 PROTECTIVES.
 EXCEPTIONS:
 1. ELEVATOR LOBBIES WITHIN AN ATRIUM.
 2. WHERE THERE ARE OPEN EXTERIOR
 CORRIDORS THE ENTIRE WIDTH OF THE
 BUILDING WITH STAIRS LOCATED AT EACH END
 AND THE ELEVATORS ARE LOCATED ON THE
 EXTERIOR OF THE BUILDING.
 3.THE MAIN ENTRANCE LEVEL OF THE
 BUILDING.
  
 412.6.2 OPENINGS IN THE ELEVATOR LOBBY
 SHALL BE LIMITED TO THOSE REQUIRED FOR
 ACCESS TO THE ELEVATORS AND FOR EGRESS
 FROM THE BUILDING. ALL ROOMS AND
 ENCLOSURES SHALL HAVE AT LEAST ONE
 REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL
 THROUGH THE ELEVATOR LOBBY.OPENINGS
 MAY BE PROVIDED WITH HORIZONTAL SLIDING
 DOORS CONFORMING TO ?1012.4.EXIT
 STAIRWAYS, CHUTES, JANITOR CLOSETS,
 GUEST ROOMS, SERVICE ROOMS, ETC., SHALL
 NOT OPEN INTO THE ELEVATOR LOBBY.
  
 412.6.3 EACH ELEVATOR LOBBY SHALL BE
 PROVIDED WITH AN APPROVED SMOKE
 DETECTOR LOCATED ON THE LOBBY CEILING.
 WHEN THE DETECTOR IS ACTIVATED,
 ELEVATOR DOORS SHALL NOT OPEN AND ALL
 CARS SERVING THAT LOBBY ARE TO RETURN TO
 THE MAIN FLOOR AND BE UNDER MANUAL
 CONTROL ONLY.IF THE MAIN FLOOR
 DETECTOR OR A TRANSFER FLOOR DETECTOR IS
 ACTIVATED, ALL CARS SERVING THE MAIN
 FLOOR OR TRANSFER FLOOR SHALL RETURN TO
 A LOCATION APPROVED BY THE FIRE
 DEPARTMENT AND BUILDING OFFICIAL AND BE
 UNDER MANUAL CONTROL ONLY.THE DETECTOR
 MAY SERVE TO CLOSE THE LOBBY DOORS.
  
 SUITE 800
 4) DEALS WITH THE ABOVE MENTIONED
 COMMENT, THAT ALL ROOMS AND ENCLOSURES
 ARE REQUIRED TO HAVE AT LEAST ONE
 REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL
 THROUGH THE ELEVATOR LOBBY. DOORWAY IS
 BLOCKED BY DESK AND A NEW DOOR WILL BE
 REQUIRED TO BLOCK THE RESTROOMS FROM THE
 ELEVATOR LOBBY.
  
 5) 704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6) DOORS THAT DO NOT MEET THE
 MANEUVERING CLEARENCES AT DOORS ARE:
 A824- AUTO CLOSER, ROOMS 812, 813 & 814.
  
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 7)609.2.1 TYPE I AND TYPE II
 CONSTRUCTION. PARTITIONS SHALL BE
 CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS.
 EXCEPTIONS:
 1. FRAMING MEMBERS MAY BE OF FIRE
 RETARDANT TREATED WOOD.
 2. POCKET DOORS AND THEIR FRAMES MAY BE
 OF WOOD.
  
 SUITE 1150
 8) THE SAME COMMENT ABOUT TENANTS HAVING
 ACCESS TO A STAIRWAY WITHOUT HAVING TO
 TRAVEL THROUGH AN ELEVATOR LOBBY HOLDS
 TRUE, SEE 412.6.1/ 412.6.2 & 412.6.3.
  
 9) ENTRY DOOR REQUIRES AN AUTOMATIC DOOR
 CLOSER ENVOKING MANEUVERING CLEARENCES
 AT DOORS 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARENCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.ALSO STORAGE
 CLOSET 1101 REQUIRES THE 18" SIDE
 CLEARENCE.
  
 10) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 SUITE 1200
 11) ELEVATOR LOBBY WORKS FOR THIS
 CONFIGURATION, BUT ON THE ELECTRICAL
 SHEET STILL INDICATES EXIT SIGNAGE WHERE
 THE DOORWAY WAS CLOSED, THERE IS NO EXIT
 SIGNAGE NOR EMERGENCY LIGHTING ON THE
 NORTH SIDE OF THE OFFICE?
  
 12)704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
2005-06-07 00:00:00COMM BOARD #53