Plan Review Notes
Plan Review Notes For Permit 05051851
Permit Number 05051851
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-08 00:00:00*********UNSAT **********
  
 1)NOTE: PLEASE SEE WIRING DIAGRAM
 SUBMITTED SHOWS A RISER DIAGRAM FOR A
 NEW SERVICE. IF A NEW SERVICEIS GOING TO
 BE INSTALLED, THIS MUST BE UNDER A
 SEPARATE PERMIT.
 PLEASE ONLY SUBMIT THE ELECTRICAL WIRING
 DIAGRAM RELATIVE TO POOL.
 IF NEW POOL PANEL IS BEING INSTALLED,
 THEN PLEASE INCLUDE OCP FROM EXISTING
 PANEL(IF EXSITNG) SIZE OF SERVICE ETC.
 PLEASE CLARIFY TYPE OF CONDUIT TO SUB
 PANEL.
 PLEASE SEE TYOE OF CONDUIT APPROVED FOR
 USE AND INSTALLATIONS. ENMT?
  
 2)NOTE: PLEASE SEE THE NUMBER OS
 CONDUCTORS FROM MAIN PANEL TO SUB PANEL.
  
 THIS SEEMS TO BE MISSING EITHER THE
 NUETRAL OER EQUIPMENT GROUNDING??
 250.110,250.24, ETC.
  
 3)NOTE: PLEASE SEE PLANS ARE BEING
 SUBMITTED SHOWING A GAS HEATER, YET,
 SPECS SUBMITTED SHOW A HEAT PUMP??
 PLEASE CORRELATE. IF HEAT PUMP, PLEASE
 SEE NEXT COMMENT.
  
 4)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS TO INCLUDE ALL NEW
 ELECTRICAL EQUIPMENT AND EXISTING
 ELECTRIC. PLEASE BE SURE ALL CONTINUOUS
 LOADS ARE SHOWN AT 125%. (HEAT-PUMP,
 POOL-PUMP) ETC.
 220.31B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]