| Plan Review Notes For Permit 05051837 |
| Permit Number |
05051837 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-15 00:00:00 | DENIED; | | | SHOW BTU LOAD FOR EACH APPIANCE AND | | | TOTAL BTU'S LOAD ON SYSTEM. | | | | | | SHOW AN ISOMETRIC DRAWING THAT CLEARLY | | | SHOWS ALL CUT SECTIONS OF PIPE, PER FBC | | | FUIL GAS. | | | | | | SUBMIT MANUFACTURES SHEETS FOR GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH FBC | | | GAS CODE SEC. 402.2. | | | | | | NO PERMIT PERTAINING TO A GENER ATOR | | | SHALL BE ISSUED UNTIL AN RES- GEN | | | APPLICATION IS APPLIED FOR , WITH REVIEW | | | BY BUILDING, ELECTRIC,ZONING, | | | MECHANICAL, AND PLUMBING |
|