Plan Review Notes For Permit 05051833
Permit Number 05051833
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-07-14 00:00:00******DENIED******
  
 PLAN REVIEW ONLY
  
 1) THE EXIT PASSAGEWAY ILLUSTRATES AN
 OVERALL HEIGHT OF 7'-0". PLEASE NOTE
 THAT NFPA 101, SECTION 7.1.5 REQUIRES A
 MINIMUM OF 90" WITH PROJECTIONS FROM THE
 CEILING NOT LESS THAN 80".
  
 2) SOME OF THE MIDDLE UNITS ONLY SHOW
 EXITING THROUGH THE ELEVATOR LOBBIES. NO
 EXIT CAN BE FOUND THAT LEADS DIRECTLY
 THE THE STAIRWELLS.
  
 3) PLEASE SHOW THE LOCATIONS OF ALL
 ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING FACILITIES.
  
 4) PLEASE INDICATE IF ACCESS INTO THE
 EXIT PASSAGEWAY IS PROVIDED, AND HOW
 WILL THAT BE ACCOMPLISHED?
  
 5) PLEASE INDICATE IF THE TRAFFIC AREA
 ABOVE THE EXIT PASSAGEWAY WILL SUPPORT
 THE LARGEST FIRE DEPARTMENT VEHICLES.
  
 6) KNOX BOXES WILL BE REQUIRED.
  
 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
 8) REENTRY INTO THE STAIRWELLS WILL BE
 REQUIRED AT THE LEVEL OF THE POOL DECK
 AREA.
  
 9) MORE DETAILS ARE NEEDED FOR THE DOORS
 IN REGARDS TO THE EXIT PASSAGEWAY.
  
 10) WHAT SAFEGUARDS WILL BE UTILIZED TO
 PREVENT THE ACCUMULATION OF CO?
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951