Plan Review Notes
Plan Review Notes For Permit 05051828
Permit Number 05051828
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-11 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE MANUFACTURER
 SPECIFICATIONS FOR THE GENERATOR.
  
 2} INDICATE THE PRIME MOVER FOR THE
 GENERATOR AND HOW STORED , IF
 APPLICABLE.(OTHER THAN NATURAL GAS).
  
 3)INDICATE GROUNDING METHOD.
  
 4} INDICATE RATING, TYPE AND LOCATION OF
 DISCONNECT PER 225.31-36 AND 230.70
 CWPB.
  
 5} PROVIDE A LOAD CALCULATIION FOR THE
 CIRCUITS INTENDED TO BE SERVED BY THE
 GENERATOR AND A PANEL SCHEDULE OF SAME.
  
 6} PROVIDE INFORMATION REGARDING HOW
 LOADS ARE TO BE TRANSFERRED. ALSO SPECS
 ON TRANSFER SWITCH.
  
 7} GIVE THE SIZE OF ALL CONDUCTORS AND
 CONDUITS BEING INSTALLED.
  
 8} THE VALUATION ON THE APPLICATION MUST
 INCLUDE ALL COST FOR THIS PROJECT,
 INCLUDING THE COST OF THE GENERATOR,
 LABOR AND MATERIAL. PLEASE CHANGE
 VALUATION ON THE APPLICATION TO REFLECT
 SAME PER 104.6.5.FBC.AND CWPB.
  
 9} THE DESIGNER OF RECORD MUST PRINT AND
 SIGN NAME ON PLANS PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved