 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PANEL DESIGNATIONS HAVE CHANGED
 AND THEIR LOCATIONS HAVE CHANGED. PANEL
 "A" WAS A NEW PANEL, NOW SHOWN AS
 EXISTING. PLEASE PROVIDE A PANEL
 SCHEDULE FOR ALL PANELS. PANEL "D" IS
 DESIGNATED AS THE "POOL PANEL", BUT THE
 POOL EQUIPMENT IS NOW LISTED IN PANEL
 "C".
  
 2} THE PANEL/CIRCUIT NUMBERS WERE NOT
 SHOWN AT THE DEVICES AS IN PREVIOUS
 PLANS, PLEASE PUT THEM BACK ON THE PLAN,
 THIS WILL ALSO HELP CLARIFY THE PANEL
 CHANGE SITUATION.
  
 3} THE TANKLESS WATER HEATER THAT WAS
 ADDED TO THE LOAD CALCULATION AT 36000
 WATTS, IS ON A 60 AMP BREAKER,
 36000/240=150 AMPS. THERE IS ANOTHER
 WATER HEATER IN WHAT IS NOW DESIGNATED
 AS PANEL "A" ALSO SHOWN AT 60 AMPS, BUT
 ON A SINGLE POLE BREAKER. PLEASE CLARIFY
 LOADS.
  
 4} THE "EXISTING POOL PANEL 'D' ", NOW
 SHOWN AT A SEPERATE LOCATION ON A WALL,
 MUST COMPLY WITH 225.31 DISCONNECTING
 MEANS AND 2580.32 GROUNDING. THESE WOULD
 BE INDICATED ON THE RISER DIAGRAM.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW