| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE PANEL DESIGNATIONS HAVE CHANGED |
| | AND THEIR LOCATIONS HAVE CHANGED. PANEL |
| | "A" WAS A NEW PANEL, NOW SHOWN AS |
| | EXISTING. PLEASE PROVIDE A PANEL |
| | SCHEDULE FOR ALL PANELS. PANEL "D" IS |
| | DESIGNATED AS THE "POOL PANEL", BUT THE |
| | POOL EQUIPMENT IS NOW LISTED IN PANEL |
| | "C". |
| | |
| | 2} THE PANEL/CIRCUIT NUMBERS WERE NOT |
| | SHOWN AT THE DEVICES AS IN PREVIOUS |
| | PLANS, PLEASE PUT THEM BACK ON THE PLAN, |
| | THIS WILL ALSO HELP CLARIFY THE PANEL |
| | CHANGE SITUATION. |
| | |
| | 3} THE TANKLESS WATER HEATER THAT WAS |
| | ADDED TO THE LOAD CALCULATION AT 36000 |
| | WATTS, IS ON A 60 AMP BREAKER, |
| | 36000/240=150 AMPS. THERE IS ANOTHER |
| | WATER HEATER IN WHAT IS NOW DESIGNATED |
| | AS PANEL "A" ALSO SHOWN AT 60 AMPS, BUT |
| | ON A SINGLE POLE BREAKER. PLEASE CLARIFY |
| | LOADS. |
| | |
| | 4} THE "EXISTING POOL PANEL 'D' ", NOW |
| | SHOWN AT A SEPERATE LOCATION ON A WALL, |
| | MUST COMPLY WITH 225.31 DISCONNECTING |
| | MEANS AND 2580.32 GROUNDING. THESE WOULD |
| | BE INDICATED ON THE RISER DIAGRAM. |
| | |