2005-06-07 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATION NOTES INDICATE
 USING EXISTING 200 AMP SERVICE. THE
 RISER INDICATES A NEW SERVICE. PLEASE
 CORRELATE.
  
 2} INDICATE HOW THE 200 AMP DISCONNECTS
 A,B&C ARE FED. THERE ARE ONLY 3
 CONDUCTORS FROM THE METER, BUT NO FEED
 THROUGH LUGS OR GUTTER INDICATED.
  
 3} THE PANELS AT THE MAIN HOUSE MUST
 HAVE DISCONNECTING MEANS PER 225.31-36.
 AND GROUNDING PER 250.32. PLEASE SHOW
 COMPLIANCE ON RISER.
  
 4} THE EQUIPMENT GROUND MUST NOT
 PARALLEL THE GROUNDING CONDUCTOR TO THE
 FIRST MEANS OF DISCONNECT PER 250.6.
  
 5}THE "SITTING ROOM" IS STILL PART OF
 THE MASTER BEDROOM AND THEREFORE MUST BE
 ARC FAULT PROTECTED PER 210.12.
  
 6} PANEL "C" CIRCUITS 21 & 23 ARE
 MISLABELED.
  
 IF THERE ARE ANY QUESTIIONS PLEASE CALL.
  