| Plan Review Notes For Permit 05051818 |
| Permit Number |
05051818 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-07 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE LOAD CALCULATION NOTES INDICATE | | | USING EXISTING 200 AMP SERVICE. THE | | | RISER INDICATES A NEW SERVICE. PLEASE | | | CORRELATE. | | | | | | 2} INDICATE HOW THE 200 AMP DISCONNECTS | | | A,B&C ARE FED. THERE ARE ONLY 3 | | | CONDUCTORS FROM THE METER, BUT NO FEED | | | THROUGH LUGS OR GUTTER INDICATED. | | | | | | 3} THE PANELS AT THE MAIN HOUSE MUST | | | HAVE DISCONNECTING MEANS PER 225.31-36. | | | AND GROUNDING PER 250.32. PLEASE SHOW | | | COMPLIANCE ON RISER. | | | | | | 4} THE EQUIPMENT GROUND MUST NOT | | | PARALLEL THE GROUNDING CONDUCTOR TO THE | | | FIRST MEANS OF DISCONNECT PER 250.6. | | | | | | 5}THE "SITTING ROOM" IS STILL PART OF | | | THE MASTER BEDROOM AND THEREFORE MUST BE | | | ARC FAULT PROTECTED PER 210.12. | | | | | | 6} PANEL "C" CIRCUITS 21 & 23 ARE | | | MISLABELED. | | | | | | IF THERE ARE ANY QUESTIIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|