| Plan Review Notes For Permit 05051818 |
| Permit Number |
05051818 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-27 00:00:00 | DENIED | | | | | | 1) EXISTING STAIRS ARE REQUIRED TO HAVE | | | HAND RAILS AND GUARDRAILS THAT COMPLY | | | WITH FBC 1007.5, 1015 AND 1026.5. | | | | | | 2) THE TYPE OF CONSTRUCTION SPECIFIED ON | | | SHEET A0 IS TYPE IV. THE EXTERIOR | | | BEARING WALLS, INTERIOR BEARING WALLS, | | | FLOOR/CEILING ASSEMBLIES AND | | | ROOF/CEILING ASSEMBLIES ARE REQUIRED TO | | | BE NON-COMBUSTIBLE FOR THIS CONSTRUCTION | | | TYPE. THE MINIMUM ALLOWABLE IS TYPE VI | | | CONSTRUCTION. | | | | | | 3) THE FLOOD ZONE ON SHEET AO IS | | | SPECIFIED AS X500. THIS PROPERTY IS | | | DESIGNED ON THE FEMA FLOOD INSURANCE | | | RATE MAP (FIRM) AS A "B" ZONE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|