Plan Review Notes
Plan Review Notes For Permit 05051818
Permit Number 05051818
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-27 00:00:00DENIED
  
 1) EXISTING STAIRS ARE REQUIRED TO HAVE
 HAND RAILS AND GUARDRAILS THAT COMPLY
 WITH FBC 1007.5, 1015 AND 1026.5.
  
 2) THE TYPE OF CONSTRUCTION SPECIFIED ON
 SHEET A0 IS TYPE IV. THE EXTERIOR
 BEARING WALLS, INTERIOR BEARING WALLS,
 FLOOR/CEILING ASSEMBLIES AND
 ROOF/CEILING ASSEMBLIES ARE REQUIRED TO
 BE NON-COMBUSTIBLE FOR THIS CONSTRUCTION
 TYPE. THE MINIMUM ALLOWABLE IS TYPE VI
 CONSTRUCTION.
  
 3) THE FLOOD ZONE ON SHEET AO IS
 SPECIFIED AS X500. THIS PROPERTY IS
 DESIGNED ON THE FEMA FLOOD INSURANCE
 RATE MAP (FIRM) AS A "B" ZONE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  