| Plan Review Notes For Permit 05051816 |
| Permit Number |
05051816 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-11 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A RISER DIAGRAM | | | INDICATING WHERE THE TRANSFER SWITCH | | | INTEGRATES IN THE SERVICE. THE NEMA-1 | | | SWITCH APPEARS TO BE LOCATED OUTDOORS | | | AND DOES NOT APPEAR TO BE SERVICE RATED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|