| Plan Review Notes For Permit 05051681 |
| Permit Number |
05051681 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-05-01 16:08:41 | GENERATOR SHOWS 27KW LOAD IS AT 31KW PLEASE CLARIFY, | | | WHERE THE 1.15% COMES FROM? | | | | | | NEED TO FIGURE LOADS ON PANELS A & B SHOW LOADS PANEL | | | MAIN IS ONLY 200 AMPS PLUS THE A/C PANEL AND PANEL "B" | | | | | | THE 10' TAP RULE SHOWS THAT THE TAP HAS TO TERMINATE IN | | | AN OVERCURRENT DEVICE 240.21(B)(1B) YOU HAVE MLO | | | PANEL. | | | | | | |
|