| Notes |
| Date |
Text |
| 2005-06-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT A-1 PLUMBING RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. CORRECT THE | | | FOLLOWING: | | | A. KITCHEN SINK IS NOT VENTED. SECTION | | | 901.2.1. | | | B. NO DRY HORIZONTAL VENTS. SECTIONS | | | 905.3 & 905.4. | | | C. WASH MACHINE IS NOT VENTED, & SHALL | | | HAVE A TRAP,A STANDPIPE, AND A | | | CLEANOUT 4' ABOVE THE FLOOR. SECTIONS | | | 708.10, 901.2.1 & 1002.1. | | | D. THE SHOWER, WATER CLOSET, AND LAV | | | ARE NOT VENTED. SECTION 909.1 | | | 2. SEE RED LINE EXAMPLES TO BE CODE | | | COMPLIANT ON ONE SET OF DRAWINGS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|