Plan Review Notes
Plan Review Notes For Permit 05051680
Permit Number 05051680
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-10 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT A RISER DIAGRAM
 INDICATING CONDUIT, CONDUCTOR SIZES AND
 CONFIGURATION. ALSO GROUNDING AND
 BONDING PER 250.50.
  
 2} THE KITCHEN RECEPTACLES MUST COMPLY
 WITH 210.52(C) SPACING AND
 210.8(A)(6),GFI.
  
 3} A RECEPTACLE MUST BE ADDED FOR THE
 A/C EQUIPMENT PER 210.63, ALSO
 210.52(E).
  
 4} THE SPRINKLER PUMP IS NOT LISTED IN
 THE LOAD CALCULATION. ADD SAME AND
 RECALCULATE. THE 150 AMP SERVICE NEEDS
 TO BE INCREASED.
  
 5} A TANKLESS WATER HEATER IS SHOWN ON
 THE PLAN, BUT THE CALCULATION IS SHOWN
 AS 5KW. PLEASE CHECK THE NAMEPLATE
 RATING AND SUBMIT SPECIFICATIONS FOR
 SAME.
  
 6} THE DISPOSAL IS NOT LISTED IN THE
 CALCULATION.
  
 7} 210.70(A)(2)(B), A LIGHT AND SWITCH
 ARE REQUIRED AT THE EXTERIOR DOORS.
  
 8} THE ENGINEERING TITLE BLOCK MUST
 CONTAIN THE CETIFICATE OF AUTHORIZATION
 (FIRM) LICENSE NUMBER PER 61G15-23.002.
 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW