| Plan Review Notes For Permit 05051680 |
| Permit Number |
05051680 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-10 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT A RISER DIAGRAM | | | INDICATING CONDUIT, CONDUCTOR SIZES AND | | | CONFIGURATION. ALSO GROUNDING AND | | | BONDING PER 250.50. | | | | | | 2} THE KITCHEN RECEPTACLES MUST COMPLY | | | WITH 210.52(C) SPACING AND | | | 210.8(A)(6),GFI. | | | | | | 3} A RECEPTACLE MUST BE ADDED FOR THE | | | A/C EQUIPMENT PER 210.63, ALSO | | | 210.52(E). | | | | | | 4} THE SPRINKLER PUMP IS NOT LISTED IN | | | THE LOAD CALCULATION. ADD SAME AND | | | RECALCULATE. THE 150 AMP SERVICE NEEDS | | | TO BE INCREASED. | | | | | | 5} A TANKLESS WATER HEATER IS SHOWN ON | | | THE PLAN, BUT THE CALCULATION IS SHOWN | | | AS 5KW. PLEASE CHECK THE NAMEPLATE | | | RATING AND SUBMIT SPECIFICATIONS FOR | | | SAME. | | | | | | 6} THE DISPOSAL IS NOT LISTED IN THE | | | CALCULATION. | | | | | | 7} 210.70(A)(2)(B), A LIGHT AND SWITCH | | | ARE REQUIRED AT THE EXTERIOR DOORS. | | | | | | 8} THE ENGINEERING TITLE BLOCK MUST | | | CONTAIN THE CETIFICATE OF AUTHORIZATION | | | (FIRM) LICENSE NUMBER PER 61G15-23.002. | | | FAC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|