| Plan Review Notes For Permit 05051674 |
| Permit Number |
05051674 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-07-13 00:00:00 | DENIED; | | | PREVIOUS PLAN REVIEW COMENTS NOT | | | ADDRESSED. | | | PIPING SCHEMATIC DOES NOT REFLECT THE | | | SPECIFICATIONS OR PIPING DIAGRAM. PIPING | | | DIAGRAM INDICATES 2 PUMPS AND SCHEMATIC | | | SHOWS ONE. SCHEMATIC SHOWS A 1" VENT FOR | | | MAIN DRAIN MAIN DRAIN DETAIL SHOWS | | | 1 1/2". | | | SCHMATIC SHOWS A VACUUM, BUT | | | SPECIFICATIONS AND PIPING DIAGRAM DO NOT | | | SHOW A VACUUM LINE. PLEASE CORRELATE | | | SCHMATIC WITH PIPING DIAGRAM AND | | | SPECIFICATIONS. SECTION 104.2.1. | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 805-6695 |
|