| Plan Review Notes For Permit 05051674 |
| Permit Number |
05051674 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-08 00:00:00 | ********** UNSAT *********** | | | | | | 1)NOTE: PLEASE INCLUDE ALL LICENSE | | | INFORMAION REQUIRED ON TITLE BLOCKS PER | | | FAC 61G15-23.002. PLEASE ALSO SEE FS | | | 471.023 | | | THIS IS REQUIRED ON ALL SHEETS WHEATHER | | | OR NOT COMMENT IS MADE BY OTHER | | | REVIEWERS. | | | | | | 2)NOTE: PLEASE SEE OVERHEAD ELECTRICAL | | | LINES ARE SHOWN WITHIN THE RESTRICATED | | | AREA PER 680.8 | | | | | | 3)NOTE: PLEASE CORRELATE PERMIT | | | APPLICATION AND PLANS. | | | PLEASE SEE PLANS SHOW A NEW HEAT PUMP, | | | NEW ELECTRICAL PANEL ETC. | | | PLEASE SUBMIT COMPLETE LOAD CALCULATIONS | | | FOR NEW HEAT PUMP. | | | PLEASEINCLUDE ALL EXISTING LOADS AND | | | SIZE OF EXISTING SERVICE. | | | | | | 4)NOTE: PLEASE SEE PLANS INDICATE AN NEW | | | PANEL. PLEASE SHOW FEEDERS,CONDUIT, OCP | | | FROM EXISTINGETC. | | | 215.5 | | | | | | 5)NOTE: PLEASE INCLUDE MANUFACTURE SPECS | | | FOR NEW HEATER SHOWING LISTING FROM A | | | NRTL. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|