| Plan Review Notes For Permit 05051661 |
| Permit Number |
05051661 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-06 00:00:00 | DENIED; | | | 1.COMPLY WITH ELECTRICAL PLAN REVIW NOTE | | | #1. ALSO PAGES 10 & 11 ARE NOT SEALED | | | AND SIGNED. | | | 2.BACKFLOW PROTECTION IS REQUIRED AT | | | WATER METER CITY ORD. # 2853-95. | | | 3.PLEASE REMOVE WATER HEATER CONNECTION | | | DETAIL IF TANKLESS HEATERS ARE BEING | | | USED. TANKES HEATERS SHOWN ON FLOOR PLAN | | | AND PAGE 10. | | | 4.SHUTOFF VALVES ARE REQUIRED FOR EACH | | | UNIT. PLEASE SHOW LOCATION ON PLANS. | | | 5. IS 2ND FLOOR SANITARY RISER RUN DOWN | | | OUTSIDE WALL AS SHOWN ON DRAWINGS? | | | 6.IF CAST IRON IS BAD ON THE INSIDE THE | | | BUILDING SEWER WILL ALSO REQUIRE | | | REPLACEMENT. SEE NOTE ON SHT 11. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|