| Plan Review Notes For Permit 05051661 |
| Permit Number |
05051661 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-15 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE ENGINEER OF RECORD MUST SIGN AND | | | SEAL PLANS PER 481.221 FS. | | | | | | 2} PROVIDE THE AIC RATING OF THE SERVICE | | | EQUIPMENT PER 110.9 & 10. | | | | | | 3} CORRECT THE NOTE REGARDING 21/2" | | | CONDUIT W/3 #2/0 FOR THE GEC.@ RISER. | | | | | | 4} THE 125AMP MAIN BREAKERS FOER APT. | | | FEEDERS ARE SMALLER THAN THE CALCULATED | | | LOAD. PLEASE CLARIFY. | | | | | | 5} VERIFY AND SUPPLY SPECIFICATIONS FOR | | | THE TANKLESS HEATER. | | | | | | 6} THE SMOKE DETECTOR IN THE BATHROOM ON | | | THE SECOND FLOOR IS IN VIOLATION OF | | | 8-1.4.2 NFPA-72. | | | | | | 7} BEDROOM #1 NEEDS AN ADDED RECEPTACLE | | | TO COMPLY WITH 210.52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|