Plan Review Notes
Plan Review Notes For Permit 05051661
Permit Number 05051661
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-15 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER OF RECORD MUST SIGN AND
 SEAL PLANS PER 481.221 FS.
  
 2} PROVIDE THE AIC RATING OF THE SERVICE
 EQUIPMENT PER 110.9 & 10.
  
 3} CORRECT THE NOTE REGARDING 21/2"
 CONDUIT W/3 #2/0 FOR THE GEC.@ RISER.
  
 4} THE 125AMP MAIN BREAKERS FOER APT.
 FEEDERS ARE SMALLER THAN THE CALCULATED
 LOAD. PLEASE CLARIFY.
  
 5} VERIFY AND SUPPLY SPECIFICATIONS FOR
 THE TANKLESS HEATER.
  
 6} THE SMOKE DETECTOR IN THE BATHROOM ON
 THE SECOND FLOOR IS IN VIOLATION OF
 8-1.4.2 NFPA-72.
  
 7} BEDROOM #1 NEEDS AN ADDED RECEPTACLE
 TO COMPLY WITH 210.52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW