Plan Review Notes For Permit 05051661
Permit Number 05051661
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-14 00:00:00DENIED
  
 1.SHOW SPACING OF BOLTS ON FRAMING AT
 CORNERS.AND FOR BOLTS HOLDING DOWN
 BOTOM PLATE.
  
 2.ENGINEER OF RECORD MUST SIGN AND
 SEAL ALL STRUCTURAL PAGES. FS 481.221
  
 3. DRAFT STOPPING IN FLOOR/CEILING
 ASSEMBLIES SHALL SEPERATE USEABLE SPACES
 INTO TWO OR MORE APPROXIMATE AREAS WITH
 NO AREA GREATER THAN 500 SQ. FT.
 SHOW HOW THIS WILL BE OBTAINED ON PLANS.
 FBC 2305.2.2 (1)
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  