Plan Review Notes
Plan Review Notes For Permit 05051520
Permit Number 05051520
Review Stop E
Sequence Number 3
Notes
Date Text
2005-08-15 00:00:00******* UNSAT 3RD REVIEW ************
  
 PLEASE SEE ALL NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEENO COMMENTS SEEMED TO HAVE
 BEEN ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE SOME CIRCUITING STILL MISSING
 ON PLANS.
 PLEASE SEE PLANS HAVE BEEN REDLINED FOR
 THESE ONPREVIOUS PLANS.
  
 2)NOTE: PLEASE SEE MISSING RECEPTS
 REQUIRED PER 210.52.
 PLEASE SEE FBC 104.2.1, TECHNICAL CODES
 MAY NOT BE REFERENCED IN WHOLE OR IN
 PART.
 PLEASE SEE LOCATIONS REDLINED ON PLANS
 AT MISSING LOCATIONS.
  
 3)NOTE: PLEASE SEE CIRCUITING OF SD'S.
 PLEASE ALSO SEE NOTES IN REF TO ARC
 FAULT PROTECTION. PLEASE SEE NOTES
 MENTIONS ARC FAULT FOR RECEPTS ONLY.
 PLEASE SEE NFPA-72 8-1.4.2.1 FOR
 PLACEMENT OF SD'S. PLEASE SEE KITCHEN
 SD: AND ACCORD TO NFPA 8-1.4.2, PLEASE
 SEE SD'S WITH/IN 3' OF BATH DRS, 20 ' OF
 COOKING APPLIANCE.
 PLEASE SEE THESE ITEMS WERE REDLINED ON
 PREVIOUS PLANS.
  
 4)NOTE: PLEASE SEE 210.12 2002 NEC,
 WHICH REQUIRES ALL "OUTLETS" IN BEDRMS
 TO BE ARC FAULT PROTECTED. PLEASE SEE
 "ELECTRICAL NOTES" ON PLANS MENTIONS
 ONLY RECEPTS. NOTED ON SD COMMENT.
 PLEASE ALSO VERIFY CIRCUITING, SD'S LTS,
 FANS ETC. SEE REDLINED PLANS.
  
 5)NOTE: PLEASE SEE 100A OCP SHOWN FOR
 RANGE ON #8 AWG. PLEASE SEE 240.4,310.16
 ETC FOR MAX OCP FOR 8KW RANGE.
 SAME COMMENT, NO CHANGE.
  
 6)NOTE: PLEASE SEE MAX OCP (60A) FOR
 WATER HEATER SHALL BE 150%. PLEASE SEE
 60A OCP SHOWN ON #10 AWG AND ON A 4.5KA
 UNIT.
 240.4,310.16,422.11E
 SAME COMMENT, NO CHANGE.
  
 7)NOTE: PLEASE SEE 240.4,310.16 ETC FOR
 MAX OCP FOR A/C UNITS ON #12. PANEL
 SCHEDULES SHOWS 40A OCP ON #12 AWG.
 PLEASE ADJUST.
 SAME COMMENT, NO CHANGE
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE NEW PANEL AND MAINS NOW
 SHOWN.
 NO CHANGES.
  
 9)NOTE: PLEASE VERIFY NEW GROUNDING
 ELECTRODE SYSTEM FOR NEW PANELS???
 PLEASE VERIFY IF GROUNDING ELECTRODE
 SYSTEM ALREADY EXISTS?
 PLEASE SEE 250.6,250.24 ETC FOR LOCATION
 OF GROUDING ELECTRODE SYSTEM.
 PREVIOUS NOTES MENTIONED TO CLARIFY
 EXISTING AND NOW PLANS SHOW A NEW SYSTEM
 ONLY TO NEW MAINS???
 250.6,250.24.
 ONLY "EQUIPMENT GROUNDING CONDUCOTRS"
 ARE REQUIRED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 10)NOTE: PLEASE SEE A GUTTER? IS NOW
 SHOWN FROM DISCONNECT TO SUB PANEL IN
 UNIT UPSTAIRS?
 PLEASE VERIFY IF GUTTER WILL INDEED BE
 INSTALLED. IF SO, PLEASE INCLUDE SIZE OF
 GUTTER ON RISER DIAGRAM.
 215.5,366
  
 11)NOTE: PLEASE SEE GARBAGE DISPOSAL IS
 SHOWN ON SMALL APPLIANCE CIRCUIT. THIS
 IS NOT PERMITTED. 210.52B1
  
 12)NOTE: PLEASE SEE NOTES WHICH WERE
 REDLINED ON PREVIOUS PLANS: "NOTES TO
 ELECTRICAL PLANS", REFERENCE WRONG NEC
 CODES FOR REQUIREMENTS.
 NOTE MENTIONS, ARC FAULT FOR RECEPTS,
 PREVIOUS NOTES:
 NOTE MENTIONS SPACING IN KITCHEN COUNTER
 PER 210.8, THIS IS PER 210.52C1, 210.8A6
 IS FOR GFI PROTECTION OF KITCHEN
 COUNTERSPACE RECEPTS.
 NOTE MENTIONS, LIGHTING OUTLETS PER
 210.72? THIS SHOUDL BE 210.70.
 THESE WERE CIRCILED AND REDLINE DON
 PREVIOUS PLANS.
  
  
 13)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND PLANS BEING REVIEWED
 WITH THE SAME COMMENTS. THIS WAS GIVEN
 AS ONLY A NOTICE ON PREVIOUS REVIEW,
 HOWEVER DUE TO PLANS WITH REPEATED
 COMMENTS, A 4X FEE HAS NOW BEEN ASSESSED
 IN THE AMOUNT OF $480.00 TO THE DESIGN
 PROFESSIONAL.
 PLEASE SEE ONE SET OF EACH SUBMITTED
 ELECTRICAL/BLDG PLANS HAVE NOW BEEN
 RETAINED FOR FILE AND POSSIBLE REVIEW BY
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'S FOR CODE COMPLIANCE AND SAID
 REPEAT COMMENTS.
 PLEASE SEE THIS FEE IS THE
 RESPONSIBILITY OF THE DESIGN
 PROFESSIONAL AND NOT OF THE OWNER OR
 CONTRACTOR. THIS FEE WHICH IS REQUIRED
 UNDER FS MUST BE PAID BEFORE PLANS MAY
 BE RE-SUBMITTED.
 IF PLANS COME BACK IN AGAIN WITH ANY OF
 THE SAME COMMENTS AS PREVIOUS REVIEWED,
 A4X FEE SHALL BE ASSCESSED.
 IT IS SUGGESTED, IF THERE ARE ANY
 QUESTIONS, A MEETING BE SET UP WITH THE
 DESIGNER, ENGINEER, CONTRACTOR AND CITY
 OF WEST PALM BEACH PLAN REVIEW STAFF.
  
 PLEASE CALL TO SET UP ANY MEETINGS WITH
 PLANS REVIEWER(S) WITH
 MR. JIM WITMER(INTERIM CHEIF PLANS
 EXAMINER).
 561-805-6715
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHALL BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  