| 2005-07-20 00:00:00 | ******* UNSAT 2ND REVIEW ************ |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE SOME NEW NOTES DUE TO |
| | INFORMATION NOW SHOWN ON PLANS. |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUTING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | SUBMITTED. |
| | PLEASE SEE SOME CIRCUITING STILL MISSING |
| | ON PLANS. |
| | |
| | 2)NOTE: PLEASE SEE MISSING RECEPTS |
| | REQUIRED PER 210.52. |
| | |
| | 3)NOTE: PLEASE SEE CIRCUITING OF SD'S. |
| | PLEASE ALSO SEE NOTES IN REF TO ARC |
| | FAULT PROTECTION. |
| | PLEASE SEE NFPA-72 8-1.4.2.1 FOR |
| | PLACEMENT OF SD'S. PLEASE SEE KITCHEN |
| | SD: AND ACCORD TO NFPA. |
| | |
| | 4)NOTE: PLEASE SEE 210.12 2002 NEC, |
| | WHICH REQUIRES ALL "OUTLETS" IN BEDRMS |
| | TO BE ARC FAULT PROTECTED. PLEASE SEE |
| | "ELECTRICAL NOTES" ON PLANS MENTIONS |
| | ONLY RECEPTS. |
| | PLEASE ALSO VERIFY CIRCUITING, SD'S LTS, |
| | FANS ETC. |
| | |
| | 5)NOTE: PLEASE SEE OCP SHOWN FOR RANGE |
| | ON #8 AWG. PLEASE SEE 240.4,310.16 ETC |
| | FOR MAX OCP FOR 8KW RANGE. |
| | |
| | 6)NOTE: PLEASE SEE MAX OCP FOR WATER |
| | HEATER SHALL BE 150%. PLEASE SEE 60A OCP |
| | SHOWN ON #10 AWG AND ON A 4.5KA UNIT. |
| | 240.4,310.16,422.11E |
| | |
| | 7)NOTE: PLEASE SEE 240.4,310.16 ETC FOR |
| | MAX OCP FOR A/C UNITS ON #12. PANEL |
| | SCHEDULES SHOWS 40A OCP ON #12 AWG. |
| | PLEASE ADJUST. |
| | |
| | 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE SEE NEW PANEL AND MAINS NOW |
| | SHOWN. |
| | |
| | 9)NOTE: PLEASE VERIFY NEW GROUNDING |
| | ELECTRODE SYSTEM FOR NEW PANELS??? |
| | PLEASE VERIFY IF GROUNDING ELECTRODE |
| | SYSTEM ALREADY EXISTS? |
| | PLEASE SEE 250.6,250.24 ETC FOR LOCATION |
| | OF GROUDING ELECTRODE SYSTEM. |
| | PREVIOUS NOTES MENTIONED TO CLARIFY |
| | EXISTING AND NOW PLANS SHOW A NEW SYSTEM |
| | ONLY TO NEW MAINS??? |
| | 250.6,250.24. |
| | ONLY "EQUIPMENT GROUNDING CONDUCOTRS" |
| | ARE REQUIRED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 10)NOTE: PLEASE SEE A GUTTER? IS NOW |
| | SHOWN FROM DISCONNECT TO SUB PANEL IN |
| | UNIT UPSTAIRS? |
| | PLEASE VERIFY IF GUTTER WILL INDEED BE |
| | INSTALLED. IF SO, PLEASE INCLUDE SIZE OF |
| | GUTTER ON RISE DIAGRAM. |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE SEE ATTACHE DCOPY OF |
| | FS553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL AND PLANS BEING REVIEWED |
| | WITH THE SAME COMMENTS. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD SHEETS SHALL BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |