Plan Review Notes
Plan Review Notes For Permit 05051520
Permit Number 05051520
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-20 00:00:00******* UNSAT 2ND REVIEW ************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW NOTES DUE TO
 INFORMATION NOW SHOWN ON PLANS.
  
 1)NOTE: PLEASE SHOW ALL CIRCUTING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE SOME CIRCUITING STILL MISSING
 ON PLANS.
  
 2)NOTE: PLEASE SEE MISSING RECEPTS
 REQUIRED PER 210.52.
  
 3)NOTE: PLEASE SEE CIRCUITING OF SD'S.
 PLEASE ALSO SEE NOTES IN REF TO ARC
 FAULT PROTECTION.
 PLEASE SEE NFPA-72 8-1.4.2.1 FOR
 PLACEMENT OF SD'S. PLEASE SEE KITCHEN
 SD: AND ACCORD TO NFPA.
  
 4)NOTE: PLEASE SEE 210.12 2002 NEC,
 WHICH REQUIRES ALL "OUTLETS" IN BEDRMS
 TO BE ARC FAULT PROTECTED. PLEASE SEE
 "ELECTRICAL NOTES" ON PLANS MENTIONS
 ONLY RECEPTS.
 PLEASE ALSO VERIFY CIRCUITING, SD'S LTS,
 FANS ETC.
  
 5)NOTE: PLEASE SEE OCP SHOWN FOR RANGE
 ON #8 AWG. PLEASE SEE 240.4,310.16 ETC
 FOR MAX OCP FOR 8KW RANGE.
  
 6)NOTE: PLEASE SEE MAX OCP FOR WATER
 HEATER SHALL BE 150%. PLEASE SEE 60A OCP
 SHOWN ON #10 AWG AND ON A 4.5KA UNIT.
 240.4,310.16,422.11E
  
 7)NOTE: PLEASE SEE 240.4,310.16 ETC FOR
 MAX OCP FOR A/C UNITS ON #12. PANEL
 SCHEDULES SHOWS 40A OCP ON #12 AWG.
 PLEASE ADJUST.
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE NEW PANEL AND MAINS NOW
 SHOWN.
  
 9)NOTE: PLEASE VERIFY NEW GROUNDING
 ELECTRODE SYSTEM FOR NEW PANELS???
 PLEASE VERIFY IF GROUNDING ELECTRODE
 SYSTEM ALREADY EXISTS?
 PLEASE SEE 250.6,250.24 ETC FOR LOCATION
 OF GROUDING ELECTRODE SYSTEM.
 PREVIOUS NOTES MENTIONED TO CLARIFY
 EXISTING AND NOW PLANS SHOW A NEW SYSTEM
 ONLY TO NEW MAINS???
 250.6,250.24.
 ONLY "EQUIPMENT GROUNDING CONDUCOTRS"
 ARE REQUIRED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 10)NOTE: PLEASE SEE A GUTTER? IS NOW
 SHOWN FROM DISCONNECT TO SUB PANEL IN
 UNIT UPSTAIRS?
 PLEASE VERIFY IF GUTTER WILL INDEED BE
 INSTALLED. IF SO, PLEASE INCLUDE SIZE OF
 GUTTER ON RISE DIAGRAM.
 215.5
  
 11)NOTE: PLEASE SEE ATTACHE DCOPY OF
 FS553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND PLANS BEING REVIEWED
 WITH THE SAME COMMENTS. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHALL BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  