| 2005-06-13 00:00:00 | ***********UNSAT ************** |
| | |
| | 1)NOTE: PLEASE CORRELATE PLANS , PERMIT |
| | APPLICATION AND SCOPE OF WORK TO BE |
| | DONE. |
| | PLEASE SEE PLANS MENTIONS, APTS, 7,9,1 |
| | AND 2?? |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | TO BE SUBMITTED. |
| | PLEASE INDICATE ALL ELECTRICAL WHICH IS |
| | EXISTING. MUST MEET 2002 NEC, OR WILL BE |
| | REQUIRED TO BE BROUGHT UP TO CODE. |
| | PLEASE SHOW ALL MIN CIRCUITING PER 2002 |
| | 210.52,210.52D,210.11C1,C2,C3 ETC. |
| | NEC.215.5 |
| | |
| | 3)NOTE: PLEASESEE BLDG REVIEW COMMENTS |
| | FOR CHANGING ONE UNIT INOT TWO AND |
| | POSSIBILITY OF TWO PERMITS REQUIRED FOR |
| | PERMITTING AND ADDRESSING OF EACH UNIT? |
| | |
| | 4)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2 |
| | FOR MISSING SD'S REQUIRED. |
| | |
| | 5)NOTE: PLEASE INCLUDE A RISER DIAGRAM |
| | SHOWING NEW PANELS/DISC'S ETC. |
| | FEEDERS, OCP, CONDUITS, GROUNDING ETC. |
| | |
| | 6)NOTE: PLEASE INCLUDE LOAD CALCUALTIONS |
| | FOR ADDED LOAD TO EXISTING? SERVICE? |
| | 220 |
| | |
| | PLEASE SEE DUE TO PLANS NOT BEING |
| | COMPLETE AT THIS TIME, THERE MAY BE |
| | COMMENTS FOR FOLLOWING REVIEW. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |