| Plan Review Notes For Permit 05051489 |
| Permit Number |
05051489 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-03-28 00:00:00 | DENIED: | | | 2ND REQUEST: | | | 1.COMMENT FROM REVIEW DATED 7/21/05 | | | WAS NOT ADDRESSED.PLEASE INDICATE | | | RETURN AIR FROM THE FAMILY ROOM SHOW | | | COMPLIANCE WITH 2001 FMC 601.4. | | | | | | NEW COMMENTS ON THE NEW MECHANICAL PLAN | | | SUBMITTED FOR REVIEW: | | | 1.THE MANUAL J & ENERGY CALCULATIONS | | | SUBMITTED AND APPROVED WITH PERMIT | | | INDICATE A PACKAGE UNIT FOR THE | | | ADDITION.THE REVISION SUBMITTED | | | INDICATES THE AIR PROVIDED FOR THE | | | ADDITION WILL BE FROM THE EXISTING | | | SYSTEM.PLEASE PROVIDE REVISED ENERGY & | | | MANUAL J CALCULATIONS.PLEASE PROVIDE | | | AN EQUIPMENT SCHEDULE. | | | | | | 2.RETURN AIR IS ALSO REQUIRED FROM THE | | | NEW STUDY AREA. | | | | | | 3.PLEASE NOTE, THE NEW BATHROOM SHALL | | | HAVE A WINDOW WITH A MINIMUM OPENING OF | | | 3 SQUARE FEET OR AN EXHAUST FAN WILL BE | | | REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|