| Notes |
| Date |
Text |
| 2005-06-13 00:00:00 | DENIED: | | | 1.ENERGY CALCULATIONS SUBMITTED ARE | | | FOR THE THE ADDITION ONLY.PLAN | | | INDICATES THE AIR TO THE ADDITION WILL | | | BE SUPPLIED FROM THE EXISTING SYSTEM. | | | PLEASE PROVIDE THE FOLLOWING: | | | A) EXISTING EQUIPMENT INFORMATION (MAKE, | | | MODEL, BTU OR TONNAGE). | | | B) PROVIDE MANUAL J CACLUATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|