| Plan Review Notes For Permit 05051451 |
| Permit Number |
05051451 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-13 00:00:00 | DENIED; | | | BACK TO BACK BATHROOMS NOT SHOWN ON A | | | RISER DIAGRAM FORM. | | | MASTER BATHROOM, HORIZONTAL DRY VENTS | | | ARE NOT PERMITED IN THE DRAINAGE SYSTEM | | | SEC. 905.3 AND 905.4. | | | RISER DIAGRAM DOESNOT MATCH FLOOR PLAN. | | | FLOOR PLAN SHOW A SHOWER IN DOWN STAIRS | | | BATHROOM RISER DIAGRAM SHOWS A TUB , | | | PLEASE CORRECT. | | | NO WALLS ARE AVALABLE ON FIRST FLOOR FOR | | | PLUMBING RISER FOR SECOND FLOOR BACK TO | | | BACK BATHROOMS.THREE 3" PVC WILL NOT FIT | | | IN A BLOCK WALL. | | | RISERS TO SECOND FLOOR CAN BE 3". | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|