| Plan Review Notes For Permit 05051451 |
| Permit Number |
05051451 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-08 00:00:00 | | | | DENIED: | | | 1. PROVIDE FOR AUX. DRAIN PAN UNDER | | | A.H.U. WITH DRAIN PROTECTION. | | | 2003 FBC/M 307.2.3 . | | | | | | 2. BEDROOMS REQUIRE BALLANCED R/A | | | 2003 FBC/M 604.1 EXCEPTION #1. | | | | | | 3. NOT ALL GRILL SIZES, & CFM'S SHOWING. | | | | | | 4. SIZES OF COPPER LINES & DRAIN LINE | | | NOT SHOWING. | | | |
|