| 2007-01-13 14:05:28 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE CIRCUITS AND OVER CURRENT |
| | PROTECTION IS NOW SHOWN FOR ITEMS ON PANEL SCHEDULES, |
| | PLEASE SEE THE CIRCUITS FOR THE WHIRLPOOL TUB AND |
| | WHIRLPOOL HEAT ARE BOTH SHOWN AT 15A CIRCUITS AND #14 |
| | WIRE, HOWEVER THE LOAD ON EACH OF THESE AS STATED ON |
| | THE LOAD CALCULATIONS IS 2000 WATTS FOR EACH WHICH |
| | EXCEEDS THE RATINGS OF THESE CIRCUITS. PLEASE CORRELATE |
| | LOADS, CIRCUIT, AND BREAKER ETC. |
| | 240.4, 310.16, 408.4, 220.14 ETC. |
| | |
| | 2) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW; PLEASE |
| | SEE 210.52B1, 210.11C1 AND 220.16 FOR CIRCUITING OF |
| | DINING ROOM. IF ON ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS THEN PLEASE ADJUST AS BEING SHOWN ON THEIR OWN |
| | CIRCUIT. |
| | PREVIOUS REVIEW NOTE. |
| | |
| | 3) NOTE: PLEASE SEE GFI DESIGNATION FOR EACH OF THE |
| | CIRCUITS FEEDING THE JACUZZI/WHIRLPOOL TUB.680.71./ |
| | PLEASE LIST EITHER ON PANEL SCHEDULE IF THE PROTECTION |
| | IS THE BREAKER OR LIST ON THE PLANS IF AT THE TUB. |
| | PREVIOUS REVIEW NOTE. |
| | |
| | 4) NOTE: PLEASE VERIFY LOAD CALCULATIONS AS SHOWN AS |
| | THE LOAD SHOWN AFTER DE-RATING AS SHOWN PLACES LOAD AT |
| | 198+ AMPS. PLEASE SEE NEC 220.31 AND 90.8 FOR ALLOWANCE |
| | AND SIZING SERVICE FOR FUTURE EQUIPMENT. THIS IS |
| | EXPLAINED IN THE HANDBOOK IN COMMENTARY. |
| | PLEASE SEE SERVICE TOTAL WATTAGE IS BEING DIVIDED BY |
| | 230V?S, PLEASE VERIFY THE VOLTAGE AND USE THE ACTUAL |
| | VOLTAGE PRESENT. IS THIS VOLTAGE NOT 240V? |
| | PLEASE SEE NOTES ABOVE AS THE LOADS ON THE WHIRLPOOL |
| | HEATER AND PUMP NEED TO BE VERIFIED ALONG WITH THE |
| | ADDITIONAL LOAD FOR DINING ROOM CIRCUIT. |
| | PLEASE VERIFY PUMP, POOL EQUIPMENT LOADS ETC AND |
| | CORRELATE. |
| | FBC ADMIN SECTION 106.3.5.4 (8). |
| | |
| | |
| | ** IF THERE ARE NAY QUESTIONS, PLEASE DO NOT HESITATE |
| | IN CONTACTING THIS OFFICE TO GO OVER COMMENTS OR |
| | QUESTIONS. THIS MAY HELP TO CLEAR UP ANY ITEMS IN |
| | QUESTION. |
| | |