| 2007-01-01 15:21:36 | |
| | |
| | ** UNSAT ** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS DONE IN AUG |
| | AND OCT OF 06 STILL NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETED PANEL SCHEDULE(S). |
| | PLEASE KNOW IT HAS COME TO THIS OFFICE ATTENTION THAT |
| | IN FACT A METER/MAIN COMBO PANEL HAS BEEN INSTALLED |
| | INSTEAD OF WHAT IS SHOWN ON RISER SUBMITTED. PLEASE |
| | SUBMIT THE PANEL SCHEDULE FOR ALL BRANCH CIRCUITS BEING |
| | FED FROM THIS OUTSIDE PANEL. |
| | PLEASE SEE THE PANEL WHICH IS BEING SHOWN AS INSIDE |
| | LISTS THE CONDENSING UNITS WHICH ARE OUTSIDE.IF THIS |
| | WERE THE CASE THEN DISCONNECTS PER 440.11 WOULD BE |
| | REQUIRED TO BE INSTALLED BACK OUTSIDE. |
| | PLEASE KNOW THAT THE PANEL SCHEDULES SHALL BE COMPLETE |
| | AND DETAILED FOR EACH CIRCUIT. |
| | PLEASE SEE PREVIOUS COMMENTS STATED THAT ALL ROOMS AND |
| | AREAS IN WHICH EACH BRANCH CIRCUIT FEEDS SHALL BE |
| | SPECIFIC. IE: BEDRM#3 LTS, LIVING RM RECEPTS, LIBRARY |
| | RECEPTS/LTS ETC ETC. |
| | 310.16, 240.4, 408.4. |
| | PLEASE SUBMIT THE PANEL SCHEDULE AND THE EQUIPMENT |
| | BEING FED FROM ANY OUTSIDE PANEL. |
| | FBC 104.2.1.2 |
| | PLEASE KNOW THERE ARE MANY ITEMS FOR COMPLETE CODE |
| | COMPLIANCE CAN NOT BE DONE AS THE PANEL SCHEDULE IS NOT |
| | YET COMPLETE WITH THE INFORMATION AS PREVIOUSLY |
| | REQUESTED. |
| | PLEASE ALSO KNOW THIS WAS A TOPIC WHICH WAS BROUGHT UP |
| | BY THE CODE MAKING PANELIST AT THE LAST IAEI STATE |
| | SECTION MEETING IN MAY OF 06 WHICH REINFORCEDTHAT OF |
| | STATED ABOVE AND WHAT IS ALREADY IN THE CODE. |
| | ALL PUBLIC AND OFFICIAL RECORD DOCUMENTS SHALL ALSO BE |
| | SPECIFIC TO DESIGN, TECHNICAL SPECIFICATIONS AND |
| | CODES. |
| | |
| | 2) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE #1, PLEASE |
| | SEE 210.52B1, 210.11C1 AND 220.16 FOR CIRCUITING OF |
| | DINING ROOM. IF ON ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS AND HOW LOADS ARE REQUIRED TO BE SHOWN. |
| | |
| | 3) NOTE: PLEASE SEE GFI DESIGNATION FOR EACH OF THE |
| | CIRCUITS FEEDING THE JACUZZI/WHIRLPOOL TUB.680.71./ |
| | PLEASE LIST EITHER ON PANEL SCHEDULE IF THE PROTECTION |
| | IS THE BREAKER OR LIST ON THE PLANS IF AT THE TUB. |
| | |
| | 4) NOTE: PLEASE KNOW, IF INDEED A METER/MAIN PANEL IS |
| | INSTALLED OUTSIDE THEN PLEASE SEE 250.6, 250.24B, |
| | 250.110 AND 250.122 FOR THE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM THE MAIN TO THE SUB PANEL. |
| | PLEASE ADJUST RISER FOR ALL OF THE ABOVE. |
| | |
| | 5) NOTE: PLEASE VERIFY LOAD CALCULATIONS AS SHOWN AS |
| | THE LOAD SHOWN AFTER DE-RATING AS SHOWN PLACES LOAD AT |
| | 198+ AMPS. PLEASE SEE NEC 220.31 AND 90.8 FOR ALLOWANCE |
| | AND SIZING SERVICE FOR FUTURE EQUIPMENT. THIS IS |
| | EXPLAINED IN THE HANDBOOK IN COMMENTARY. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |