Plan Review Notes
Plan Review Notes For Permit 05051450
Permit Number 05051450
Review Stop E
Sequence Number 6
Notes
Date Text
2007-01-01 15:21:36 
  
 ** UNSAT **
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS DONE IN AUG
 AND OCT OF 06 STILL NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SUBMIT COMPLETED PANEL SCHEDULE(S).
 PLEASE KNOW IT HAS COME TO THIS OFFICE ATTENTION THAT
 IN FACT A METER/MAIN COMBO PANEL HAS BEEN INSTALLED
 INSTEAD OF WHAT IS SHOWN ON RISER SUBMITTED. PLEASE
 SUBMIT THE PANEL SCHEDULE FOR ALL BRANCH CIRCUITS BEING
 FED FROM THIS OUTSIDE PANEL.
 PLEASE SEE THE PANEL WHICH IS BEING SHOWN AS INSIDE
 LISTS THE CONDENSING UNITS WHICH ARE OUTSIDE.IF THIS
 WERE THE CASE THEN DISCONNECTS PER 440.11 WOULD BE
 REQUIRED TO BE INSTALLED BACK OUTSIDE.
 PLEASE KNOW THAT THE PANEL SCHEDULES SHALL BE COMPLETE
 AND DETAILED FOR EACH CIRCUIT.
 PLEASE SEE PREVIOUS COMMENTS STATED THAT ALL ROOMS AND
 AREAS IN WHICH EACH BRANCH CIRCUIT FEEDS SHALL BE
 SPECIFIC. IE: BEDRM#3 LTS, LIVING RM RECEPTS, LIBRARY
 RECEPTS/LTS ETC ETC.
 310.16, 240.4, 408.4.
 PLEASE SUBMIT THE PANEL SCHEDULE AND THE EQUIPMENT
 BEING FED FROM ANY OUTSIDE PANEL.
 FBC 104.2.1.2
 PLEASE KNOW THERE ARE MANY ITEMS FOR COMPLETE CODE
 COMPLIANCE CAN NOT BE DONE AS THE PANEL SCHEDULE IS NOT
 YET COMPLETE WITH THE INFORMATION AS PREVIOUSLY
 REQUESTED.
 PLEASE ALSO KNOW THIS WAS A TOPIC WHICH WAS BROUGHT UP
 BY THE CODE MAKING PANELIST AT THE LAST IAEI STATE
 SECTION MEETING IN MAY OF 06 WHICH REINFORCEDTHAT OF
 STATED ABOVE AND WHAT IS ALREADY IN THE CODE.
 ALL PUBLIC AND OFFICIAL RECORD DOCUMENTS SHALL ALSO BE
 SPECIFIC TO DESIGN, TECHNICAL SPECIFICATIONS AND
 CODES.
  
 2) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE #1, PLEASE
 SEE 210.52B1, 210.11C1 AND 220.16 FOR CIRCUITING OF
 DINING ROOM. IF ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS AND HOW LOADS ARE REQUIRED TO BE SHOWN.
  
 3) NOTE: PLEASE SEE GFI DESIGNATION FOR EACH OF THE
 CIRCUITS FEEDING THE JACUZZI/WHIRLPOOL TUB.680.71./
 PLEASE LIST EITHER ON PANEL SCHEDULE IF THE PROTECTION
 IS THE BREAKER OR LIST ON THE PLANS IF AT THE TUB.
  
 4) NOTE: PLEASE KNOW, IF INDEED A METER/MAIN PANEL IS
 INSTALLED OUTSIDE THEN PLEASE SEE 250.6, 250.24B,
 250.110 AND 250.122 FOR THE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM THE MAIN TO THE SUB PANEL.
 PLEASE ADJUST RISER FOR ALL OF THE ABOVE.
  
 5) NOTE: PLEASE VERIFY LOAD CALCULATIONS AS SHOWN AS
 THE LOAD SHOWN AFTER DE-RATING AS SHOWN PLACES LOAD AT
 198+ AMPS. PLEASE SEE NEC 220.31 AND 90.8 FOR ALLOWANCE
 AND SIZING SERVICE FOR FUTURE EQUIPMENT. THIS IS
 EXPLAINED IN THE HANDBOOK IN COMMENTARY.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]