| Plan Review Notes For Permit 05051450 |
| Permit Number |
05051450 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-08-19 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT 18 0F 18 SANT. RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. PLEASE MAKE | | | CHANGES TO RISER DIAGRAM THAT ARE SHOWN | | | ON THE FLOOR PLAN. SECTION 106.3.5.1.3. | | | | | | 2. SHT 18 OF 18 INDICATE ALL PIPE SIZES | | | ON THE RISER DIAGRAM. TABLES 710.1(1) & | | | 710.1(2). | | | | | | 3. ALL SHEETS SHALL BEAR THE NAME AND | | | SIGNATURE OF THE PERSON DESIGNING THE | | | PLANS. 106.1.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|