Plan Review Notes
Plan Review Notes For Permit 05051450
Permit Number 05051450
Review Stop M
Sequence Number 3
Notes
Date Text
2006-08-11 00:00:00*** DENIED ***
 **FIRST FLOOR**
 1) NEED TO SHOW CFM'S AT THE KITCHEN
 SUPPLY AIR GRILL.
  
 2) NEED RETURN AIR DUCTS SIZED TO
 STORAGE ROOM #115, LIBRARY #109, AND
 LIVING ROOM #101.
  
 3) RETURN AIR GRILL NEAR THE T-STAT.
 NEEDS TO BE SIZED.
  
 4) 8X13 SUPPLY AIR TRUNK LINE IS TO
 SMALL FOR A 4 TON SYSTEM, PLEASE CORRECT
 OR SUBMIT MANUAL D CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R
 M1601.1 AND FBC 13-610.1.ABC.1 .
  
 ** SECOND FLOOR **
 5) RTURN AIR TRANSFER DUCT TO MASTER
 BEDROOM SUITE NEEDS TO BE 18", SEE NOTE
 #7.
  
 6) THERE IS NO SUPPLY AIR DUCT TO THE
 GRILL IN BEDROOM #2, IF NEED CORRECT THE
 RETURN AIR TRANSFER DUCT, SEE NOTE #7.
  
 7) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2001 FBC/M 601.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  