Plan Review Notes
Plan Review Notes For Permit 05051450
Permit Number 05051450
Review Stop M
Sequence Number 2
Notes
Date Text
2005-09-06 00:00:00*** PROVISO ***
 1) MASTER BEDROOM RETURN AIR DUCT TO
 A.H.U. NEEDS TO BE 12" .
 2) 2ND. FLOOR HALL RETURN AIR DUCT TO
 A.H.U. NEEDS TO BE 14" .
 3) MASTER BATHROOM NEEDS AN EXHAUST FAN,
 IF THERE IS NO WINDOW OPENING OF 3 FT.
 PER. FBC/M 402.3.1.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6712.