Plan Review Notes
Plan Review Notes For Permit 05051450
Permit Number 05051450
Review Stop E
Sequence Number 2
Notes
Date Text
2005-08-31 00:00:00******** UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NOTES FROM CHANGES
 MADE TO PLANS.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE KNOW, THIS IS REQUIRED ON PLANS
 FOR RATINGS OF EQUIPMENT.
 RESPONSE LTR MENTIONS, BY OTHERS?
 FPL LTR IN PACKAGE MENTIONS AVAILABLE
 FAULT CURRENT AT 29,000 + AFC.
 THIS IS REQUIRED ON PLANS AT THIS TIME.
 PREVIOUS NOTES;
  
 2)NOTE: PLEASE SEE LOCATION OF PANEL
 WHICH WAS IN LAUNDRY RM HAS NOW BEEN
 MOVED INTO STORAGE ROOM. PLEASE SEE THE
 ELECTRICAL PANEL CONTAINING OVERCURRENT
 DEVICES SHALL NOT BE INSTALLED IN
 STORAGE/ CLOSET AREAS WITH COMBUSTIBLES.
 110.26,408.7,240.24 ETC.
  
 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 THIS WAS ON PREVIOUS NOTES.
  
 4)NOTE: PLEASE CORRELATE LOAD
 CALCULATIONS AND PANEL SCHEDULE
 SUBMITTED FOR AHU'S AND # OF CIRCUITS.
 PLEASE SEE ONLY ONE AHU IS INDICATED ON
 PANEL SCHEDULE.
 PLEASE SEE THE NUMBER OF POLES ON PANEL
 SCHEDULE FOR CIRCUITS, SEEMS TO EXCEED
 THE MAXIMUM OF 42 POLES.
 408.15
 PLEASE ADJUST.
 PREVIOUS NOTE;
  
 5)NOTE: PLEASE SEE DISPOSAL IS SHOWN
 WITH A 2KW LOAD. PLEASE SEE A MAX OF 80%
 LOAD SHALL BE FIGURED FOR A 1-POLE 20A
 CIRCUIT. (1920VA).
 PLEASE VERIFY KW RATING FOR DISPOSAL.??
  
 6)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 *** PLEASE KNOW, THESE PLANS OR PREVIOUS
 PLANS DO NOT CONTAIN AN DEVICE OR
 FIXTURE LEGEND FOR ELECTRICAL PLANS.
 PLEASE SUBMIT.
  
 7)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 NFPA-72 8-1.4.1.6.2
 PREVIOUS NOTES.
  
 8)NOTE: PLEASE SEE FBC 104.2.1, CITY OF
 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS, WHICH REQUIRES THE PRINTED
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS AND DESIGN.
  
 9)NOTE: PLEASE PLACE ROOM/AREA
 DESIGNATIONS ON ELECTRICAL PLANS.
 PLEASE CLARIFY "GALLERY" AS NOTED ON
 ARCH SHEETS. THIS AREA SEEMS TO BE A
 "HALLWAY" ? PLEASE SEE 210.52H FOR
 RECEPT SPACING.
  
 10)NOTE: PLEASE SEE HWH SEEMS TO
 INDICATE A 220V RECEPT FOR "PLUGGING-IN"
 OF WATER HEATER?
 PLEASE INDICATE A DISCONNECT AS
 REQUIRED.422.31B ETC.
 WATER HEATERS ARE NOTE "LISTED" FOR CORD
 AND PLUG CONNECTIONS.
  
 11)NOTE: PLEASE INDICATE THE REQUIRED
 CONNECTIONS FOR GROUNDING ELECTRODE PER
 250.50.
 FOOTER STEEL AND COLD WATER PIPE(IF
 METAL).
  
 12)NOTE; PLEASE SEE RECEPT IN LAUNDRY RM
 UPSTAIRS SHALL BE INDICATED AS GFI.
 210.8A
  
 13)NOTE: PLEASE SEE TWO A/C SYSTEMS ARE
 SHOWN ON PANEL SCHEDULE AND LOADS,
 HOWEVER ONLY ONE COND UNIT COULD BE
 LOCATED ON PLANS?
 PLEASE SHOE AND PLEASE INDICATE DISC PER
 440.1, AND WP GFI PER 210.63.
  
 14)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND PLANS WITH REPEAT CODE
 COMPLIANCE COMMENTS. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 PLEASE BE SURE ANY VOIDED SHEETS ARE
 REMOVED FROM SETS AND INSERT NEW SHEETS.
 THIS WAS DONE FROM PREVIOUS SUBMITTED
 AND ONLY A NOTICE FOR SHEETS TO BE
 CHANGED OUT.
  
 PLEASE SEE ANY POSSIBEL COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  