| Date |
Text |
| 2005-08-31 00:00:00 | ******** UNSAT 2ND REVIEW ********* |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE SOME NOTES FROM CHANGES |
| | MADE TO PLANS. |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE KNOW, THIS IS REQUIRED ON PLANS |
| | FOR RATINGS OF EQUIPMENT. |
| | RESPONSE LTR MENTIONS, BY OTHERS? |
| | FPL LTR IN PACKAGE MENTIONS AVAILABLE |
| | FAULT CURRENT AT 29,000 + AFC. |
| | THIS IS REQUIRED ON PLANS AT THIS TIME. |
| | PREVIOUS NOTES; |
| | |
| | 2)NOTE: PLEASE SEE LOCATION OF PANEL |
| | WHICH WAS IN LAUNDRY RM HAS NOW BEEN |
| | MOVED INTO STORAGE ROOM. PLEASE SEE THE |
| | ELECTRICAL PANEL CONTAINING OVERCURRENT |
| | DEVICES SHALL NOT BE INSTALLED IN |
| | STORAGE/ CLOSET AREAS WITH COMBUSTIBLES. |
| | 110.26,408.7,240.24 ETC. |
| | |
| | 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | THIS WAS ON PREVIOUS NOTES. |
| | |
| | 4)NOTE: PLEASE CORRELATE LOAD |
| | CALCULATIONS AND PANEL SCHEDULE |
| | SUBMITTED FOR AHU'S AND # OF CIRCUITS. |
| | PLEASE SEE ONLY ONE AHU IS INDICATED ON |
| | PANEL SCHEDULE. |
| | PLEASE SEE THE NUMBER OF POLES ON PANEL |
| | SCHEDULE FOR CIRCUITS, SEEMS TO EXCEED |
| | THE MAXIMUM OF 42 POLES. |
| | 408.15 |
| | PLEASE ADJUST. |
| | PREVIOUS NOTE; |
| | |
| | 5)NOTE: PLEASE SEE DISPOSAL IS SHOWN |
| | WITH A 2KW LOAD. PLEASE SEE A MAX OF 80% |
| | LOAD SHALL BE FIGURED FOR A 1-POLE 20A |
| | CIRCUIT. (1920VA). |
| | PLEASE VERIFY KW RATING FOR DISPOSAL.?? |
| | |
| | 6)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | *** PLEASE KNOW, THESE PLANS OR PREVIOUS |
| | PLANS DO NOT CONTAIN AN DEVICE OR |
| | FIXTURE LEGEND FOR ELECTRICAL PLANS. |
| | PLEASE SUBMIT. |
| | |
| | 7)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | NFPA-72 8-1.4.1.6.2 |
| | PREVIOUS NOTES. |
| | |
| | 8)NOTE: PLEASE SEE FBC 104.2.1, CITY OF |
| | WEST PALM BEACH ADMINISTRATIVE |
| | AMENDMENTS, WHICH REQUIRES THE PRINTED |
| | NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLANS AND DESIGN. |
| | |
| | 9)NOTE: PLEASE PLACE ROOM/AREA |
| | DESIGNATIONS ON ELECTRICAL PLANS. |
| | PLEASE CLARIFY "GALLERY" AS NOTED ON |
| | ARCH SHEETS. THIS AREA SEEMS TO BE A |
| | "HALLWAY" ? PLEASE SEE 210.52H FOR |
| | RECEPT SPACING. |
| | |
| | 10)NOTE: PLEASE SEE HWH SEEMS TO |
| | INDICATE A 220V RECEPT FOR "PLUGGING-IN" |
| | OF WATER HEATER? |
| | PLEASE INDICATE A DISCONNECT AS |
| | REQUIRED.422.31B ETC. |
| | WATER HEATERS ARE NOTE "LISTED" FOR CORD |
| | AND PLUG CONNECTIONS. |
| | |
| | 11)NOTE: PLEASE INDICATE THE REQUIRED |
| | CONNECTIONS FOR GROUNDING ELECTRODE PER |
| | 250.50. |
| | FOOTER STEEL AND COLD WATER PIPE(IF |
| | METAL). |
| | |
| | 12)NOTE; PLEASE SEE RECEPT IN LAUNDRY RM |
| | UPSTAIRS SHALL BE INDICATED AS GFI. |
| | 210.8A |
| | |
| | 13)NOTE: PLEASE SEE TWO A/C SYSTEMS ARE |
| | SHOWN ON PANEL SCHEDULE AND LOADS, |
| | HOWEVER ONLY ONE COND UNIT COULD BE |
| | LOCATED ON PLANS? |
| | PLEASE SHOE AND PLEASE INDICATE DISC PER |
| | 440.1, AND WP GFI PER 210.63. |
| | |
| | 14)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONALS AND PLANS WITH REPEAT CODE |
| | COMPLIANCE COMMENTS. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | PLEASE BE SURE ANY VOIDED SHEETS ARE |
| | REMOVED FROM SETS AND INSERT NEW SHEETS. |
| | THIS WAS DONE FROM PREVIOUS SUBMITTED |
| | AND ONLY A NOTICE FOR SHEETS TO BE |
| | CHANGED OUT. |
| | |
| | PLEASE SEE ANY POSSIBEL COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |