| 2005-06-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SHT 18 OF 18 SANT. RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. CORRECT THE | | | FOLLOWING: | | | A. TUB NOT VENTED 2ND FLOOR GUEST ROOM | | | BATHROOM. | | | B. KITCHEN SINK SHALL NOT DRAIN THRU | | | THE HORIZONTAL WET VENT FOR THE POWDER | | | ROOM FIXTURES. SECTION 909.1. - KITCHEN | | | SINKS SHALL DISCHARGE DOWNSTREAM OF THE | | | POWDER ROOM FIXTURES. | | | C. KITCHEN SINK IN THE ISLAND. INDICATE | | | HOW THIS CAN BE VENTED THRU THE ROOF | | | WITH NO WALL NEXT TO THE SINK. SUGGEST | | | USE OF AN AIR ADMITTENCE VALVE, OR AN | | | ISLAND VENT. SECTIONS 913, OR 917. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|