2005-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT 18 OF 18 SANT. RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. TUB NOT VENTED 2ND FLOOR GUEST ROOM
 BATHROOM.
 B. KITCHEN SINK SHALL NOT DRAIN THRU
 THE HORIZONTAL WET VENT FOR THE POWDER
 ROOM FIXTURES. SECTION 909.1. - KITCHEN
 SINKS SHALL DISCHARGE DOWNSTREAM OF THE
 POWDER ROOM FIXTURES.
 C. KITCHEN SINK IN THE ISLAND. INDICATE
 HOW THIS CAN BE VENTED THRU THE ROOF
 WITH NO WALL NEXT TO THE SINK. SUGGEST
 USE OF AN AIR ADMITTENCE VALVE, OR AN
 ISLAND VENT. SECTIONS 913, OR 917.
  