| 2005-06-16 00:00:00 | DENIED: |
| | 1.RETURN AIR JUMPERS ARE NOT SIZED |
| | PROPERLY.PER 2001 FBC(M)601.4 |
| | EXCEPTION #1 & 3, RETURN AIR JUMPERS |
| | SHALL BE A MINIMUM OF 1 1/2 TIMES |
| | (SQUARE INCHES) LARGER THAN THE SUPPLY |
| | AIR TO THAT AREA.ALL AIR INTO THE |
| | MASTER SUITE IS TO BE INCLUDED: |
| | LIBRARY 7" SUPPLY = 9" R/A JUMPER |
| | GUEST RM 8" SUPPLY = 10" R/A JUMPER |
| | BEDRM 2 & 3 8" SUPPLY = 10" R/A JUMPER |
| | MASTER SUITE 10" & 8" SUPPLY=16" R/A |
| | |
| | 2.TWO COPIES OF ALL SPECIFICATIONS |
| | REQUIRED PER 2001 FBC 104.2.1.TWO SETS |
| | OF PLANS WERE SUBMITTED BUT NOT THE |
| | PRODUCT APPROVALS OR ENERGY |
| | CALCULATIONS. |
| | |
| | 3.PROVIDE MANUAL J CALCULATIONS IN |
| | ACCORDANCE WITH 2001 FBC CHATPER 6. |
| | |
| | 4.PROVIDE VENTING LAYOUT & MATERIAL |
| | FOR THE DRYER EXHAUST VENT. |
| | |
| | 5.CONDENSATE SHALL TERMINATE A MINIMUM |
| | OF 12" FROM THE BUILDING STRUCTURE PER |
| | 2001 FBC 1503.4.4. |
| | |
| | 6.PROVIDE AUXILIARY DRAIN PAN WITH |
| | OVER FLOW PROTECTION.INDICATE WHICH |
| | METHOD OF OVERFLOW PROTECTION WILL BE |
| | USED.2001 FBC(M)307.2.3. |
| | |