Plan Review Notes
Plan Review Notes For Permit 05051450
Permit Number 05051450
Review Stop M
Sequence Number 1
Notes
Date Text
2005-06-16 00:00:00DENIED:
 1.RETURN AIR JUMPERS ARE NOT SIZED
 PROPERLY.PER 2001 FBC(M)601.4
 EXCEPTION #1 & 3, RETURN AIR JUMPERS
 SHALL BE A MINIMUM OF 1 1/2 TIMES
 (SQUARE INCHES) LARGER THAN THE SUPPLY
 AIR TO THAT AREA.ALL AIR INTO THE
 MASTER SUITE IS TO BE INCLUDED:
 LIBRARY 7" SUPPLY = 9" R/A JUMPER
 GUEST RM 8" SUPPLY = 10" R/A JUMPER
 BEDRM 2 & 3 8" SUPPLY = 10" R/A JUMPER
 MASTER SUITE 10" & 8" SUPPLY=16" R/A
  
 2.TWO COPIES OF ALL SPECIFICATIONS
 REQUIRED PER 2001 FBC 104.2.1.TWO SETS
 OF PLANS WERE SUBMITTED BUT NOT THE
 PRODUCT APPROVALS OR ENERGY
 CALCULATIONS.
  
 3.PROVIDE MANUAL J CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC CHATPER 6.
  
 4.PROVIDE VENTING LAYOUT & MATERIAL
 FOR THE DRYER EXHAUST VENT.
  
 5.CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  
 6.PROVIDE AUXILIARY DRAIN PAN WITH
 OVER FLOW PROTECTION.INDICATE WHICH
 METHOD OF OVERFLOW PROTECTION WILL BE
 USED.2001 FBC(M)307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.