Plan Review Notes
Plan Review Notes For Permit 05051450
Permit Number 05051450
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF THE SERVICE
 EQUIPMENT PER 215.5.
  
 2} INDICATE THE A.I.C. RATING OF THE
 SERVICE EQUIPMENT PER 110.9 & 10.
  
 3} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH 210.52(C), SPACING ,
 AND 210.8 (A)(6), GFI.
  
 4} RECEPTACLES IN THE GALLERY MUST
 COMPLY WITH 210.52(A), SPACING.
  
 5} PLEASE SEE THE HEAT STRIPS INDICATED
 IN THE CALCULATIONS @ 20,000, DO NOT
 CORRELATE WITH THE PANEL SCHEDULE.
  
 6} PLEASE LIST THE REQUIRED BATH
 CIRCUITS ON THE PANEL SCHEDULE PER
 210.11(C)(3).
  
 7} PLEASE LIST THE REQUIRED ARC FAULT
 CIRCUITS ON THE PANEL SCHEDULE PER
 210.12.
  
 8} A SMOKE DETECTOR IS REQUIRED AT THE
 STAIRWELL ON BOTH LEVELS PER 905.2.2
 FBC.
  
 7} MASTER AND BEDROOM #2 NEED ADDED
 RECEPTACLES TO COMPLY WITH 210.52(A)(1)
 & (2). SEE REVIEWED SET FOR APPROXIMATE
 AREAS AND LOCATIONS.
  
 PLEASE REMOVE REVIEWED SET AND REPLACE
 WITH CORRECTED SHEETS. ALSO PLEASE
 FURNISH THE REVIEWED SET FOR REFERENCE,
 AND RESUBMIT FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved