| Date |
Text |
| 2005-06-09 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} INDICATE THE LOCATION OF THE SERVICE |
| | EQUIPMENT PER 215.5. |
| | |
| | 2} INDICATE THE A.I.C. RATING OF THE |
| | SERVICE EQUIPMENT PER 110.9 & 10. |
| | |
| | 3} THE KITCHEN COUNTERTOP RECEPTACLES |
| | MUST COMPLY WITH 210.52(C), SPACING , |
| | AND 210.8 (A)(6), GFI. |
| | |
| | 4} RECEPTACLES IN THE GALLERY MUST |
| | COMPLY WITH 210.52(A), SPACING. |
| | |
| | 5} PLEASE SEE THE HEAT STRIPS INDICATED |
| | IN THE CALCULATIONS @ 20,000, DO NOT |
| | CORRELATE WITH THE PANEL SCHEDULE. |
| | |
| | 6} PLEASE LIST THE REQUIRED BATH |
| | CIRCUITS ON THE PANEL SCHEDULE PER |
| | 210.11(C)(3). |
| | |
| | 7} PLEASE LIST THE REQUIRED ARC FAULT |
| | CIRCUITS ON THE PANEL SCHEDULE PER |
| | 210.12. |
| | |
| | 8} A SMOKE DETECTOR IS REQUIRED AT THE |
| | STAIRWELL ON BOTH LEVELS PER 905.2.2 |
| | FBC. |
| | |
| | 7} MASTER AND BEDROOM #2 NEED ADDED |
| | RECEPTACLES TO COMPLY WITH 210.52(A)(1) |
| | & (2). SEE REVIEWED SET FOR APPROXIMATE |
| | AREAS AND LOCATIONS. |
| | |
| | PLEASE REMOVE REVIEWED SET AND REPLACE |
| | WITH CORRECTED SHEETS. ALSO PLEASE |
| | FURNISH THE REVIEWED SET FOR REFERENCE, |
| | AND RESUBMIT FOR REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |