| Date |
Text |
| 2005-12-03 00:00:00 | ------------------DENIED---------------- |
| | |
| | 1) DUCT SIZES, GRILL DESIGNATION AND CFM |
| | MISSING IN SUITES 104 THRU 110 AND 204 |
| | THRU 208. PLEASE INCLUDE ALL NECESSARY |
| | INFORMATION ON PLAN. |
| | |
| | 2) KEY NOTES 5,6,7 ON PAGES M2 AND M3 |
| | REFER TO DETAIL 1/M7 FOR DUCT/DIFFUSER |
| | SIZES AND LAYOUT. THIS DETAIL CONTAINS |
| | NO SUCH INFORMATION. |
| | |
| | 3) KEY NOTES 5,6,7 ON PAGES M4 AND M5 |
| | REFER TO DETAIL 1/M8 FOR DUCT/DIFFUSER |
| | SIZES AND LAYOUT. THIS DETAIL CONTAINS |
| | NO SUCH INFORMATION. |
| | |
| | 4) VAV T1-14 ON PAGE M2 REFERENCES KEY |
| | NOTE 4 (FIRE DAMPER EXCEPTION). DUCT IS |
| | NOT SHOWN TO RUN THE MIN. 5' PAST THE |
| | RATED WALL TO MEET THE CONDITIONS OF THE |
| | FIRE DAMPER EXCEPTION. |
| | |
| | 5) PAGE M5 SUITE 209 SHOWS A 24X18 DUCT |
| | FEEDING VAV T2-20 AND T2-21 EXCLUSIVELY. |
| | THE TWO VAVS COMBINED CALL FOR A TOTAL |
| | OF 270 CFM. IS THIS INTENTIONAL? |
| | |
| | 6) GENERAL HVAC NOTE #9 CALLS FOR DUCT |
| | SMOKE DETECTORS IN ALL 4 AC SYSTEMS |
| | BASED ON CFMS.PLEASE INDICATE ON PLAN |
| | THE LOCATION OF DUCT SMOKE DETECTORS, |
| | ENSURING SERVICE/INSPECTION ACCESS AND |
| | COMPLIANCE WITH MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT |
| | RONALD J REGUEIRO AT 561.805.6734 OR |
| | PATTY KRAUS AT 561.805.6719 |