| Plan Review Notes For Permit 05051446 |
| Permit Number |
05051446 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-02-08 00:00:00 | ******* UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE SOME NOTES FROM | | | PREVIOUS REVIEW WHICH NEED TO BE | | | ADDRESSED. | | | | | | | | | | | | | | | 1)NOTE: OK | | | | | | 2)NOTE: OK | | | | | | 3)NOTE:? THIS IS UNCLEAR, AS LIGHTING | | | LOADS ON "AM" SCHEDULE DO NOT SEEM TO | | | CORRELATE WITH CALCS SHOWN ONE-1 | | | | | | **PLEASE SEE THAT ALL CONTINUOUS | | | LOADS ARE SHOWN ON LOAD CALCULATIONS | | | INCLUDING ANY LARGEST MOTOR LOADS AT | | | 125%. | | | 215.3,230.42 ETC. | | | PLEASE SEE ONLY EXT LTS SEEM TO BE SHOWN | | | AT 125%. | | | | | | 4)NOTE: NO, ? SEE NOTE ABOVE AS, THE | | | LOADS ON "AM" SHOULD BE THE SAME AS | | | SHOWN FOR MAIN BLDG SERVICE? | | | PLEASE VERIFY WHY THIS IS SHOWN | | | SUBSTANTIALLY LARGER. | | | | | | **PLEASE CORRLELATE LOADS SHOWN ON | | | MSB "AM" WITH RISER | | | CALCULATIONS/LOAD(S). | | | 215.5 | | | | | | 5)NOTE: OK | | | | | | ** PLEASE CALL TO GO OVER COMMENTS AS | | | SHEETS FOR INTERIOR WALLS ETC MAY BE | | | STAMPED IF NEEDED FOR INSPECTIONS ONCE | | | FIRE REVIEW IS DONE AND PASSED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATEIN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER' | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|