| Plan Review Notes For Permit 05051446 |
| Permit Number |
05051446 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-01 00:00:00 | DENIED: | | | 1.PLAN SHEET M-4, SUPPLY AND RETURN | | | AIR DUCT PENETRATING TENANT SEPARATION | | | BETWEEN SUITE 206 & 205, FIRE DAMPERS | | | ARE NOT INDICATED ON THE PLAN. | | | | | | 2.PROVIDE DETAIL OF THE SHAFT ENCLOSER | | | INDICATED ON PLAN SHEET M-5.PLEASE | | | NOTE, FIRE DAMPER REQUIRED WHERE DUCT | | | PENETRATES THE SHAFT WALL 2001 FBC | | | 705.1.2.2.1. | | | | | | 3.PLEASE INDICATE PROTECTION FOR DUCT | | | DUCTS SERVING THE FIRST FLOOR. 2001 | | | FBC(M) 607.4. | | | | | | 4.PLAN SHEET M-7 KEY NOTE #3 | | | REFERENCES DUCT PENETRATION DETAIL | | | 7/S-1.PLEASE CLARIFY LOCATION OF THE | | | DETAIL? | | | | | | 5.PROVIDE TIE DOWN & SUPPORT DETAIL | | | FOR RTU CURB SHOWN ON PLAN SHEET M-8. | | | | | | 6.PLEASE NOTE, ENGINEER IS REQUIRED TO | | | HAVE IS PRINTED NAME & LICENSE NUMBER | | | INDICATED ON EACH PLAN SHEET IN | | | ACCORDANCE WITH FS 471.025 & FAC | | | 61G15-23.002.CERTIFICATE OF | | | AUTHORIZATION (BUSINESS NUMBER) SHALL | | | ALSO BE IDENTIFIED ON THE TITLE BLOCK. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|