| Plan Review Notes For Permit 05051446 |
| Permit Number |
05051446 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-21 00:00:00 | BUILDING PROVISOS: | | | | | | 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 2)705.7.1 JOINTS INSTALLED IN OR BE- | | | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- | | | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES | | | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- | | | ING ASSEMBLIES SHALL BE PROTECTED BY AN | | | APPROVED FIRE RESISTANT JOINT SYSTEM | | | DESIGNED TO RESIST THE PASSAGE OF FIRE | | | FOR A PERIOD NOT LESS THAN THE RE- | | | QUIRED FIRE RESISTANCE RATING OF THE | | | WALL, FLOOR OR FLOOR IN OR BETWEEN | | | WHICH IT IS INSTALLED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|